Low level configuration (RogerVDM) 

Programming procedure with RogerVDM software (firmware 1.1.30.266 or newer): 

1.  Connect the device to RUD-1 interface (fig. 8) and connect the RUD-

1 to computer’s USB port. 

2.  Remove jumper from MEM contacts (fig. 4) if it is placed there. 
3.  Restart  the  device  (switch  power  supply  off  and  on  or  short  RST  contacts  for  a  moment)  and  orange 

LED SYSTEM will pulsate. Then within 5 seconds place jumper on MEM contacts. 

4.  Start  RogerVDM  program,  select 

MCT

  device,  firmware  version, 

RS485

  communication  channel  and 

serial port with RUD-1 interface. 

5.  Click 

Connect,

 the program will establish connection and will automatically display 

Configuration

 tab. 

6.  Enter unoccupied RS485 address in range of 100-115 and other settings according to requirements of 

specific installation. 

7.  Click 

Send to Device

 to update the configuration of device. 

8.  Optionally make a backup by clicking 

Send to File… 

and saving settings to file on disk. 

9.  Disconnect from RUD-1 interface and leave jumper on MEM contacts to enable further configuration of 

device from VISO v2 software or remove jumper from MEM contacts to block such remote configuration. 

Programming procedure with RogerVDM software (firmware older than 1.1.30.266): 

1.  Connect the reader to RUD-1 interface (fig. 8) and connect the RUD-

1 to computer’s USB port. 

2.  Place jumper on MEM contacts (fig. 4). 
3.  Restart  the  reader  (switch  power  supply  off  and  on  or  short  RST  contacts  for  a  moment)  and  orange 

LED SYSTEM will pulsate. 

4.  Start  RogerVDM  program,  select 

MCT

  device,  firmware  version, 

RS485

  communication  channel  and 

serial port with RUD-1 interface. 

5.  Click 

Connect,

 the program will establish connection and will automatically display 

Configuration

 tab. 

6.  Enter unoccupied RS485 address in range of 100-115 and other settings according to requirements of 

specific installation. 

7.  Click 

Send to Device

 to update the configuration of device. 

8.  Optionally make a backup by clicking 

Send to File… 

and saving settings to file on disk. 

9.  Remove jumper from MEM contacts and disconnect device from RUD-1 interface. 

Note: Do not read any cards when reader is configured with RogerVDM. 

 

Fig. 8 Connection to RUD-1 interface (low level configuration) 

Table 5. List of low level parameters 

Communication settings 

RS485 address 

Parameter  defines  device  address  on  RS485  bus.  Range:  100-115. 

Summary of Contents for MCT82M-IO-HR

Page 1: ...Roger Access Control System MCT82M IO HR Operating Manual Product version 1 0 Firmware version 1 1 18 or newer Document version Rev D ...

Page 2: ...n key bell 3 parametric EOL inputs 2 transistor outputs 1 relay output RS485 interface Tamper protection Screw terminals Power supply The terminal requires power supply voltage in range of 11 15VDC It can be supplied from MCX2D MCX4D expander of MC16 PAC KIT from MC16 access controller e g TML output or from dedicated power supply unit The supply wire diameter must be selected in such way that the...

Page 3: ...p The matching resistors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc but the recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong electromagnetic interferences The RS485 communica...

Page 4: ... DO NOT DISTURB Red Requires programming Fig 3 Indicators and function key Note Synchronic pulsing of all four LEDs signifies lost communication with MC16 controller Buzzer The terminal is equipped with buzzer which is used to signal integral functions and it can be additionally programmed with other available functions within high level configuration VISO Inputs The terminal offers 3 general purp...

Page 5: ...t is operated in such way that CA contacts opening is interpreted as triggering of the first input while CB opening is interpreted as triggering of the second input In VISO software DW input type is represented by two independent inputs Each can be used for different purpose and assigned with different function Parametric resistors The same values of parametric resistors are used for all inputs i ...

Page 6: ...onfiguration VISO v2 or RogerVDM Function are assigned to outputs within high level configuration VISO Multiple functions with different priorities can be assigned to the same output at the same time Identification By default the terminal reads serial numbers CSN of MIFARE cards but it is possible to program cards with own numbers PCN in selected and encrypted sectors of card memory The use of PCN...

Page 7: ...t panel Note MCT82M IO HR enclosure consists of front panel and back panel New device is assembled with a standard back panel but additional free of charge extended back panel is included This panel can be used when connection cable has to be hidden and no flush mounting box is available ...

Page 8: ...MCT82M IO HR Operating Manual Rev D doc 22 06 2021 8 17 Fig 5 MCT82M IO HR installation ...

Page 9: ...MCT82M IO HR Operating Manual Rev D doc 22 06 2021 9 17 Fig 6 MCT82M IO HR F installation ...

Page 10: ... s power supply line and RS485 bus are connected directly to the controller The terminal can also operate with MC16 controller using MCX2D MCX4D expanders as in case of M16 PAC KIT series Fig 7 Typical connection diagram for the terminal and MC16 access controller 4 CONFIGURATION The purpose of low level configuration is to prepare device for operation in RACS 5 system In case of RACS 5 v1 system ...

Page 11: ...onfiguration of device from VISO v2 software or remove jumper from MEM contacts to block such remote configuration Programming procedure with RogerVDM software firmware older than 1 1 30 266 1 Connect the reader to RUD 1 interface fig 8 and connect the RUD 1 to computer s USB port 2 Place jumper on MEM contacts fig 4 3 Restart the reader switch power supply off and on or short RST contacts for a m...

Page 12: ... Yes Keypad settings Keypad activated Parameter enables deactivation of keypad Range 0 No 1 Yes Default value 1 Yes Advanced settings Stop card PIN reading when buffer full Parameter enables to reject card PIN reading by device till previous card PIN is transmitted to controller Range 0 No 1 Yes Default value 0 No Card PIN buffer timeout s Parameter defines time for card PIN storing in device buff...

Page 13: ...r where PCN is stored Range 0 39 Default value 1 Application ID AID Parameter defines application ID number AID which indicates sector where PCN number is stored Range 0 9999 Default value 5156 Block ID Parameter defines block number where PCN is stored Range 0 2 to for sectors 0 31 and 0 14 for sectors 32 39 Default value 0 Key type Parameter defines key type used to access sector with PCN Range ...

Page 14: ...s application key number used for file read Range 0 13 Default value 0 Key type Parameter defines encryption key type for Desfire file Range 0 TDES Native 1 TDES Standard 2 3 KTDES 3 AES128 Default value 0 TDES Native Key Parameter defines access key for Desfire file with PCN 3 KTDES key is 24 bytes 48 HEX digits TDES and AES keys are 16 bytes 32 HEX digits Manual addressing Manual addressing proc...

Page 15: ...e jumper on MEM contacts fig 4 3 Restart the device switch power supply off and on or short RST contacts for a moment and orange LED SYSTEM will pulsate 4 Read any MIFARE card 11 times 5 Wait till device confirms reset with long acoustic signal 6 Remove jumper from MEM contacts and restart the device High level configuration VISO The purpose of high level configuration is to define logical functio...

Page 16: ... Two IO1 IO2 open collector outputs 15VDC 150mA max load Tamper protection Enclosure opening reported to access controller Proximity cards 13 56MHz MIFARE Ultralight Classic DESFire EV1 and Plus Reading range Up to 7 cm for MIFARE Ultralight Classic Up to 4 cm for MIFARE DESFire EV1 Plus Distance 1200m maximal cable length for RS485 bus between controller and reader IP Code IP41 Environmental clas...

Page 17: ...IO HR v1 0 06 2018 The first commercial version of product This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your...

Reviews: