HRT82TS Installation Guide Rev.C.doc
2016-10-10
7/9
Fig. 6 Device select window in RogerVDM software
Fig. 7 Configuration window in RogerVDM software
Table 3. Configuration parameters
Parameter
Values
Description
General
Device Name
16 ASCII
characters
Device description which can be filled with any comment by
installer.
Transmission Format
RACS CLK/DTA
Reader Address
0..15
Device address on RACS CLK/DTA bus. Default address ID=7
is required for communication with HRC controller.
Communication
timeout
0..255
The device signals communication failure when selected
timeout [0.5s] elapses. When 0 is selected then failure is not
signalled at all.
4.2 Firmware update
HRT82TS firmware can be updated with RogerVDM (available at
www.roger.pl
) after connection to
RUD-1 communication interface.
Firmware update procedure
1.
Connect device to RUD-1 communication interface according to fig. 5
2.
Install and start RogerVDM software
3.
Close
Select Device window
4.
In top menu select
Tools->Update firmware
5.
In the opened window select device, port with connected RUD-1 and specify path to firmware
file (*.hex) – see fig. 8
6.
According to displayed message place jumper on FDM pins and restart the device (place and
remove jumper on RST pins or switch power supply off and on)
7.
Select
Update button
8.
After firmware upload remove jumper from FDM pins and reset device (place and remove
jumper on RST pins or switch power supply off and on)