HRT82TS Installation Guide Rev.C.doc

 

2016-10-10 

 

 

6/9 

 

4.

 

C

ONFIGURATION

 

4.1 Device programming 

The address of factory new HRT82TS is ID=7 and such device is ready to communicate with HRC 
series  controller  requiring  no additional configuration. The same address  is  used  by  HRT82AC  air 
conditioning control panel. Therefore particular controller can operate with only one of mentioned 

devices at the same time.  
If  necessary,  HRT82TS  settings  can  be  modified  with  RogerVDM  software  (available  at 

www.roger.pl

) after connection to RUD-1 communication interface. 

 

 

Fig. 5 HRT82TS and RUD-1 connection 

Connection and configuration procedure 

1.

 

Connect device to RUD-1 communication interface according to fig. 5 

2.

 

Place jumper on MEM pins 

3.

 

Restart the device (place and remove jumper on RST pins or switch power supply off and on) 

4.

 

Install and start RogerVDM software 

5.

 

In the opened window select device, firmware version, communication channel and serial port 

with connected RUD-1 – see fig. 6 

6.

 

Select 

Connect button, the software shall establish connection with the device and automatically 

switch to configuration window 

7.

 

Enter required settings (configuration window is shown in fig. 7, while options are described in 

table 3) 

8.

 

Select 

Send to Device button – the software shall upload new settings 

9.

 

Remove jumper from MEM pins 

10.

 

Restart the device (place and remove jumper on RST pins or switch power supply off and on) 

Note: 

During  connection  procedure  placing  jumper  on  MEM  pins  and  restarting  the  device  restores  its 
factory default settings. 

Summary of Contents for HRT82TS

Page 1: ...re version 1 0 8 23 or newer Hardware version 1 0 Document version Rev C 2016 ROGER sp z o o sp k All rights reserved This document is subject to the Terms of Use in their current version published at the www roger pl website of the Roger sp z o o sp k company hereinafter referred to as ROGER ...

Page 2: ...bles room temperature readout allowing the controller to control air conditioning and or heating systems Interchangeably room temperature can also be read by means of such devices with built in temperature sensors as HRT82AC air conditioning control panel and HRT82MF CH card holder Table 1 Specification Supply voltage Nominal 12VDC min max range 10 15VDC Average current consumption 25mA Tamper res...

Page 3: ...nominal power supply The power must be connected to 12V and GND terminals Additionally the GND terminal is used as reference potential for the RACS CLK DTA bus HRT82TS power supply can be provided by connection to buffer power supply unit e g PS 15DR PS20 or connection to AUX output of HRC402DR controller see fig 2 Backup battery connected to power supply unit or directly to HRC402DR controller ca...

Page 4: ... of front panel and base which are factory assembled and require manual disassembly prior to installation according to fig 4 Installation guidelines Install device on wall far from sources of heat and moisture It is recommended to install device on Ø60mm flush mounting box Front panel and base must be properly oriented in order to ensure functioning of tamper resistance All electric connections mu...

Page 5: ...HRT82TS Installation Guide Rev C doc 2016 10 10 5 9 Fig 4 HRT82TS latches and wall mounting ...

Page 6: ...on interface according to fig 5 2 Place jumper on MEM pins 3 Restart the device place and remove jumper on RST pins or switch power supply off and on 4 Install and start RogerVDM software 5 In the opened window select device firmware version communication channel and serial port with connected RUD 1 see fig 6 6 Select Connect button the software shall establish connection with the device and autom...

Page 7: ...en failure is not signalled at all 4 2 Firmware update HRT82TS firmware can be updated with RogerVDM available at www roger pl after connection to RUD 1 communication interface Firmware update procedure 1 Connect device to RUD 1 communication interface according to fig 5 2 Install and start RogerVDM software 3 Close Select Device window 4 In top menu select Tools Update firmware 5 In the opened wi...

Page 8: ...see 4 1 5 TROUBLESHOOTING Table 4 Troubleshooting Issue Visual indication Acoustic indication Solution No communication with controller Front panel icon backlight blinking 1 Check if RACS CLK DTA bus is properly connected wires are undamaged and the bus does not exceed 150 m All devices connected to particular RACS CLK DTA bus should have common supply minus GND 2 Check if the controller is proper...

Page 9: ...is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment Weight of the equipment is specif...

Reviews: