2-10
Programming and Parameters
MO
T
O
R CO
NTR
O
L
Vo
lt
s p
er
H
er
tz
069
[Start Boost]
Sets the voltage boost level for starting
and acceleration. Refer to parameter 083
[Overspeed Limit].
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Motor NP Volts]
×
0.25
0.1 VAC
071
[Break Voltage]
Sets the voltage the drive will output at
[Break Frequency]. Refer to parameter
083 [Overspeed Limit].
Default:
Min/Max:
Units:
[Motor NP Volts]
×
0.25
0.0/[Motor NP Volts]
0.1 VAC
072
[Break Frequency]
Sets the frequency the drive will output at
[Break Voltage]. Refer to parameter 083.
Default:
Min/Max:
Units:
[Motor NP Hz]
×
0.25
0.0/[Maximum Freq]
0.1 Hz
File
Gr
oup
No.
Parameter Name & Description
Values
Related