Programming and Parameters
2-7
Motor Control File
MO
NI
T
O
R
Metering
022
[Ramped Speed]
Value of commanded speed after Accel/
Decel, and S-Curve are applied.
Default:
Min/Max:
Units:
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
023
[Speed Reference]
Summed value of ramped speed, process
PI and droop.
Default:
Min/Max:
Units:
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
025
[Speed Feedback]
This parameter displays the estimated
value of actual motor speed.
Default:
Min/Max:
Units:
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Dr
iv
e D
at
a
026
[Rated kW]
Drive power rating.
Default:
Min/Max:
Units:
Read Only
0.00/3000.00 kW
0.01 kW
027
[Rated Volts]
The drive input voltage class (208, 240,
400 etc.).
Default:
Min/Max:
Units:
Read Only
0.0/690.0 VAC
0.1 VAC
028
[Rated Amps]
The drive rated output current.
Default:
Min/Max:
Units:
Read Only
0.0/6553.5 Amps
0.1 Amps
029
[Control SW Ver]
Main Control Board software version.
Default:
Min/Max:
Units:
Read Only
0.000/255.255
0.001
File
Gr
oup
No.
Parameter Name & Description
Values
Related
Fil
e
Gr
oup
No.
Parameter Name & Description
Values
Related
MO
T
O
R CO
NTR
O
L
Motor Data
040
[Motor Type]
Set to match the type of motor connected.
Default:
Options:
0
0
“Induction”
“Induction”
041
[Motor NP Volts]
Set to the motor nameplate rated volts.
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Rated Volts]
0.1 VAC
042
[Motor NP FLA]
Set to the motor nameplate rated full load
amps.
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Rated Amps]
×
2
0.1 Amps
043
[Motor NP Hertz]
Set to the motor nameplate rated
frequency.
Default:
Min/Max:
Units:
Based on Drive Cat. No.
5.0/320.0 Hz
0.1 Hz
044
[Motor NP RPM]
Set to the motor nameplate rated RPM.
Default:
Min/Max:
Units:
1750.0 RPM
60.0/19200.0 RPM
1.0 RPM
045
[Motor NP Power]
Set to the motor nameplate rated power.
Default:
Min/Max:
Units:
Based on Drive Rating
0.00/5000.00
0.01 kW/HP
See