
12
Publication SAFETY-AT017B-EN-P – July 2011
Edit the Module’s Input Configuration
1.
Select the Input Configuration tab.
2.
Select one of the following under Point Mode:
•
Standard – Input circuits not tested internally
•
Safety – Input circuits tested internally
•
Safety Pulse Test – Input circuits tested internally and wired
to a Test Source for Pulse-Testing
3.
Select Inputs 0 and 1 for the E-stop.
These are configured as Safety Pulse Test and utilize Test Sources
0 and 1, respectively.
4.
Select Inputs 2 and 3 for the Interlock Switch.
These are configured as Safety Pulse Test and utilize Test Sources
0 and 1, respectively.
5.
Select Inputs 4 and 5 for the Safety Circuit and Fault Reset
buttons.
These are not safety inputs so they are configured as Standard.
6.
Select Input 7
to monitor the feedback from the Safe-Off relay in
the PowerFlex 70 drive.
This is a Standard input.
Edit the Module’s Test Output Configuration
1.
Select the Test Output tab.
2.
Configure Test Outputs 0 and 1 as Pulse Test.