Installation Guidelines
Follow these guidelines to make sure that your VersaView® 6300B box PC or VersaView 6300T box thin client provides service with excellent reliability.
•
When choosing the installation site, consider the following:
- The site must have sufficient power
- The site must be indoors and non-hazardous
- The site must not expose the computer to direct sunlight
•
The box PC or box thin client can operate in a surrounding air temperature range as follows:
- 0…55 °C (32…131 °F) with the Intel Atom x5 processor
- 0…50 °C (32…122 °F) with the Intel Atom x7 processor
- 0…50 °C (32…122 °F) with the Intel Core i3, Core i5, and Core i7 processors
The surrounding air temperature must not exceed the maximum temperature for your box PC or box thin client, especially when either one is mounted in an enclosure.
•
The box PC or box thin client can be stored in a surrounding air temperature range of -10…+60 °C (14…140 °F).
•
The humidity of the surrounding air must not exceed 80% noncondensing.
Mounting Requirements
Follow these requirements to mount the VersaView 6300B box PCs or VersaView 6300T box thin clients.
•
Choose a suitable mounting height.
•
Only mount the box PC or box thin client in a vertical (upright) position, where the ground screw is at the bottom, as shown in
•
Mount the box PC or box thin client so there is at least 20 mm (0.8 in.) of clearance on each side for the circulation necessary for cooling.
Required Tools and Hardware for Installation
The following tools are needed for the mounting bracket installations.
•
A drill and 4 mm drill bit
•
#2 Phillips screwdriver
•
Four M4x20 stainless steel screws (customer supplied)
•
Safety glasses
Install a Box PC or Box Thin Client With the Book Mount Bracket
Install the box PC or box thin client in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.
1.
to locate and drill holes for the four M4x20 stainless steel screws.
2.
Install the four customer-supplied screws but leave enough space to hang the brackets.
3.
Align the keyhole slots on the top bracket with the top two screws.
4.
Align the slots on the bottom bracket with the bottom two screws.
5.
Slide the computer downward until all four screws are at the top of each bracket slot.
6.
Tighten the four screws.
Install a Box PC With the DIN Rail Bracket
Install the box PC in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.
1.
Refer to the 6300B-DRF
x
Box PC dimensions in
.
2.
Install the box PC on a DIN rail.
ATTENTION:
For DIN rail mounting applications, only safety glasses are needed.
IMPORTANT
A DIN rail is not supplied with the bracket. An installed DIN rail is the responsibility of the customer.