4

5-Pin Unit

Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2.

 Replace the 

2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

Note: 

If the user does not require the Auxiliary signal, a 4-pin 

cordset (889D-F4AC-2) can be used.

Recommended patchcord for use with ArmorBlock® Guard 

Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2.

 Replace the 2 with 

0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable 
lengths.

Note:

 Do not use a 5-pin patchcord with the ArmorBlock.

Diagnostic

Unit Indicators (per IEC 60073)

Pin Number

Signal

1

+24V

2

OSSD 1

3

0V

4

OSSD 2

5

Aux.

Device 

Output 

LED

State

Status

Troubleshooting

Off

Not Powered

NA

Red

Not Safe, OSSD not active

NA

Green

Safe, OSSD active

NA

Green Flash

Power up test or OSSD 

inputs not valid

Check 24V DC or OSSD 

inputs (yellow and red wire)

Red Flash

1 Hz Flash Recoverable Fault

4 Hz Flash Non-recoverable 

Fault

Recoverable fault —check 

OSSD outputs are not 

shorted to GND, 24V DC or 

each other. Cycle power.

Amber Flash

(-N  & -N9 

models only)

1 Hz Flash margin indicator

Safe, OSSD active

Sensor is reaching max. 

sensing distance; realign 

sensor with actuator

Refer to Technical Specifications (page 1) for 
certification information and ratings.

1

5

2

4

3

IMPORTANT

Summary of Contents for SensaGuard 440N-Z21SS2 Series

Page 1: ...el campo de b squeda PORTUGUESE Esta folha de instru es est dispon vel em v rias l nguas em www rockwellautomation com literature Seleccione a l ngua de publica o e entre com SensaGuard no espa o de b...

Page 2: ...h other Mount the switch and actuator to removable guard door or gate Keep the switch and actuator within the sensing range shown in the sensing misalignment curve Nut Torque Specification Switch Actu...

Page 3: ...TANC E when the actuator approaches the sensor in the x direction or from above z direction and is misaligned in the y direction Sensor Actuator Misalignment mm Assured Make 15 mm Assured OFF 35 mm x...

Page 4: ...mber Signal 1 24V 2 OSSD 1 3 0V 4 OSSD 2 5 Aux Device Output LED State Status Troubleshooting Off Not Powered NA Red Not Safe OSSD not active NA Green Safe OSSD active NA Green Flash Power up test or...

Page 5: ...Flashing to indicate Series inputs are not 24V Actuator 5 is in sensing range Switch 5 is functioning properly Series inputs are 0V OSSDs are de energized to 0V Green LED is Flashing to indicate Seri...

Page 6: ...y Pink Yellow Red Brown SensaGuard Unit 1 SensaGuard Unit 2 SensaGuard Unit 3 GuardShield Blue Gray Pink Yellow Red Brown Blue Gray Pink Yellow Red Brown Blue Gray Pink Brown A1 S11 S52 S12 13 23 33 4...

Page 7: ...ite Black SensaGuard Integrated Latch Reset Gate Open Grey IMPORTANT 889D F8AB A1 S11 S21 S12 S22 S32 L11 Y32 L12 13 14 S42 23 24 S34 A2 DI 440R D22R2 0 1 2 3 4 5 6 7 8 LOGIC K1 K2 K1 K2 S11 S12 S21 S...

Page 8: ...witching circuit Also check for signs of abuse or tampering Inspect the switch casing for damage Repair If there is any malfunction or damage no attempts at repair should be made The unit should be re...

Reviews: