Install the Drive
2-1
C
HAPTER
2
Install the Drive
Review all installation and wiring instructions thoroughly before proceeding.
Throughout the installation procedures, use figure 1.1 to locate wiring termination
points.
Plan the installation to ensure acceptable environmental and operating conditions for
the drive. Read and follow the requirements given below before proceeding with the
installation:
Figure 2.1 – Access Clearances and Installation Guidelines
!
ATTENTION: Only qualified electrical personnel, familiar with the
construction and operation of this equipment and the hazards involved,
should install, adjust, operate, and/or service this equipment. Read and
understand this instruction manual in its entirety before proceeding.
Failure to observe this precaution could result in severe bodily injury or
loss of life.
ATTENTION: This equipment is at line voltage when AC power is
connected. Disconnect and lockout all ungrounded conductors of the
AC power line before working on the unit. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: The user is responsible for conforming with all applicable
local and national codes. Failure to observe this precaution could result
in severe bodily injury or loss of life.
•
Locate the drive where it will have unrestricted
clearance as shown. Mount the drive on a flat
surface.
•
Locate the drive where it will be kept clean (away
from oil, coolants, or airborne contaminants).
•
Verify that the ambient temperature will remain
between 0
°
C to 50
°
C (32
°
F to 122
°
F).
•
Verify that the relative humidity will be between 0%
and 95%, non-condensing.
•
For installations above 1000 meters (3300 feet),
refer to Appendix A for derating guidelines.
•
Verify that there will be adequate clearance for fan
intake.
•
When using the optional local keypad, 25.4 mm
(1.0 in) clearance is required on the right side only
for installing/removing the keypad.
38.1
38.1
[1.50]