Installation/Wiring
2-1
C
HAPTER
2
Installation/Wiring
This chapter provides information on mounting and wiring the Reach Drive.
Most start-up difficulties are the result of incorrect wiring. Every precaution must be
taken to assure that the wiring is done as instructed. All items must be read and
understood before the actual installation begins
2.1
AC Supply Source Considerations
Reach Drives are suitable for use on a circuit capable of delivering up to a maximum
of 200,000 rms symmetrical amperes and a maximum of 600 volts.
If a system ground fault monitor (RCD) is to be used, only Type B (adjustable) devices
should be used to avoid nuisance tripping.
!
ATTENTION:
The following information is merely a guide for proper
installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or
otherwise for the proper installation of this drive or associated equipment.
A hazard of personal injury and/or equipment damage exists if codes are
ignored during installation.
!
ATTENTION:
To guard against personal injury and/or equipment
damage caused by improper fusing or circuit breaker selection, use only
the recommended line fuses/circuit breakers specified in Appendix A.