Rockwell Automation Publication 6000-IN100B-EN-P - October 2020
67
Appendix D Power Cabling and Control Signal Wiring Details
Emergency Stop
X
2436/2437
2439/2440
X
Emergency Stop Interlock
Hardwired in series with Emergency
Stop PB on Door
MV permissive to close (NO)
X
D-758/D758A
X
Status of permission to close
MV (NO) - permission when
closed
NO Relay contacts from interposing
relay driven by PIOB - DO1
MV permissive to close (NC)
X
D-759/D759A
X
Status of permission to close
MV (NC) - permission when
open
NC Relay contacts from interposing
relay driven by PIOB - DO1
MV device closed (NO)
X
D-760/D760A
X
Status of MV device feedback
(NO) - closed when closed
NO Relay contacts from interposing
relay driven by MV Device Status
from customer
MV device closed (NC)
X
D-761/D761A
X
Status of MV device feedback
(NC) - open when closed
NC Relay contacts from interposing
relay driven by MV Device Status
from customer
Drive Alarm (NO)
X
D-752/D752A
-89D6
Drive Warning Status (NO) -
warning when closed
NO Relay contacts from interposing
relay driven by POD Port 7 - RO0
Drive Alarm (NC)
X
D-753/D753A
-89D6
Drive No Warning Status (NO) -
no warning when closed
NC Relay contacts from interposing
relay driven by POD Port 7 - RO0
Drive Fault (NO)
X
D-748/D748A
-89D6
Drive Fault Status (NO) - faulted
when closed
NO Relay contacts from interposing
relay driven by POD Port 7 - RO1
Drive Fault (NC)
X
D-749/D749A
-89D6
Drive Not Faulted Status (NO) -
not faulted when closed
NC Relay contacts from interposing
relay driven by POD Port 7 - RO1
Drive Running (NO)
X
D-744/D744A
-89D6
Drive Running Status (NO) -
running when closed
NO Relay contacts from interposing
relay driven by POD Port 8 - RO1
Drive Running (NC)
X
D-745/D745A
-89D6
Drive Not Running Status (NO) -
not running when closed
NC Relay contacts from interposing
relay driven by POD Port 8 - RO1
Drive Ready (NO)
X
D-740/D740A
-89D6
Drive Ready Status (NO) - ready
when closed
NO Relay contacts from interposing
relay driven by POD Port 8 - RO0
Drive Ready (NC)
X
D-741/D741A
-89D6
Drive Not Ready Status (NO) -
not ready when closed
NC Relay contacts from interposing
relay driven by POD Port 8 - RO0
Remote Selected (NO)
X
D-762/D762A
-3LL/-3LB
Remote is selected for control
source (NO) - remote selected
when closed
NO Relay contacts from interposing
relay driven by Local/Remote
Selector switch
Remote Selected (NC)
X
D-763/D763A
-3LL/-3LB
Remote is selected for control
source (NC) - remote selected
when open
NC Relay contacts from interposing
relay driven by Local/Remote
Selector switch
DCS Selected (NO)
X
D-764/D764A
-3LB
DCS is selected for control
source (NO) - DCS selected
when closed
NO Relay contacts from interposing
relay driven by Local/Remote/DCS
Selector switch
DCS Selected (NC)
X
D-765/D765A
-3LB
DCS is selected for control
source (NC) - DCS selected
when open
NC Relay contacts from interposing
relay driven by Local/Remote/DCS
Selector switch
Table 15 - I/O Connections related to Remote Distributed Control System (Continued)
Signal Name
AI
AO
DI
DO
Wire Numbers
Standard
Drive
Option
Code
Signal Usage
Signal Logic