PowerFlex 400P Adjustable Frequency AC Drive Quick Start
English-23
A153 [PID Feedback Sel]
0/8
0 = “Analog In 1”
1 = “Analog In 2”
2 = “Comm Port”
3 = “ACT1 - ACT2”
4 = “ACT1 + ACT2”
5 = “ACT1 * ACT2”
6 = “ACT1 / ACT2”
7 = “Min A1, A2”
8 = “Max A1, A2”
0
A154 [PID Prop Gain]
0.00/99.99
0.01
1.00
A155 [PID Integ Time]
0.0/999.9 Secs
0.1 Secs
2.0 Secs
A156 [PID Diff Rate]
0.00/99.99 (1/Secs)
0.01 (1/Secs)
0.00 (1/Secs)
A157 [PID Setpoint]
0.0/100.0%
0.1%
0.0%
A158 [PID Deadband]
0.0/10.0%
0.1%
0.0%
A159 [PID Preload]
0.0/320.0 Hz
0.1 Hz
0.0 Hz
A160 [Process Factor]
0.1/999.9
0.1
30.0
A163 [Auto Rstrt Tries]
0/9
1
0
A164 [Auto Rstrt Delay]
0.0/160.0 Secs
0.1 Secs
1.0 Secs
A165 [Start At PowerUp]
0/1
0 = “Disabled”
1 = “Enabled”
0
A166 [Reverse Disable]
0/1
0 = “Rev Enabled”
1 = “Rev Disabled”
0
A167 [Flying Start En]
0/1
0 = “Disabled”
1 = “Enabled”
0
A168 [PWM Frequency]
2.0/8.0, 10.0 kHz
0.1 kHz
4.0 kHz
A169 [PWM Mode]
0/1
0 = “Space Vector”
1 = “2-Phase”
1
A170 [Boost Select]
0/15
Settings in % of base voltage.
4
Only active when A125 [Torque Perf Mode] is
set to 0 “V/Hz”.
Frames C-F
Frames G-H
0 = “Custom V/Hz”
0 = “Custom V/Hz”
1 = “30.0, VT”
1 = “30.0, VT”
2 = “35.0, VT”
2 = “35.0, VT”
3 = “40.0, VT”
3 = “40.0, VT”
4 = “45.0, VT”
4 = “45.0, VT”
5 = “0.0, no IR”
5 = “0.0, no IR”
6 = “0.0”
6 = “0.0”
7 = “2.5, CT”
7 = “0.2”
8 = “5.0, CT”
8 = “0.5”
9 = “7.5, CT”
9 = “0.8”
10 = “10.0, CT”
10 = “1.0”
11 = “12.5, CT”
11 = “2.0”
12 = “15.0, CT”
12 = “3.0”
13 = “17.5, CT”
13 = “4.0”
14 = “20.0, CT”
14 = “5.0”
15 = “Kepco”
15 = “Kepco”
A171 [Start Boost]
0.0/25.0%
1.1%
2.5%
Only active when A170 [Boost Select] and L361 [Torque Perf Mode] are set to “0”.
A172 [Break Voltage]
0.0/100.0%
0.1%
25.0%
Only active when A170 [Boost Select] and L361 [Torque Perf Mode] are set to “0”.
A173 [Break Frequency]
0.0/320.0 Hz
0.1 Hz
15.0 Hz
Only active when A170 [Boost Select] and L361 [Torque Perf Mode] are set to “0”.
A174 [Maximum Voltage]
20/Rated Volts
1 VAC
Rated Volts
A175 [Slip Hertz @ FLA]
0.0/10.0 Hz
0.1 Hz
2.0 Hz
A176 [DC Brake Time]
0.0/99.9 Secs
0.1 Secs
0.0 Secs
A177 [DC Brake Level]
0.0/(Drive Amps
×
1.5) 0.1 Amps
Amps
×
0.05
A178 [DC Brk Time@Strt]
0.0/99.9 Secs
0.1 Secs
0.0 Secs
A179
A180
[Current Limit 1]
[Current Limit 2]
0.0/(Drive Amps
×
1.5) 0.1 Amps
Amps
×
1.1
A181 [Motor OL Select]
0/2
0 = “No Derate”
1 = “Min Derate”
2 = “Max Derate”
0
A182 [Drive OL Mode]
0/3
0 = “Disabled”
1 = “Reduce CLim”
2 = “Reduce PWM”
3 = “Both-PWM 1st”
3
A183 [SW Current Trip]
0.0/(Drive Amps
×
1.8) 0.1 Amps
0.0 (Disabled)
A184 [Load Loss Level]
0.0/Drive Amps
0.1 Amps
0.0 (Disabled)
A185 [Load Loss Time]
0/9999 Secs
1 Secs
0 (Disabled)
A186 [Stall Fault Time]
0/5
0 = “60 Seconds”
1 = “120 Seconds”
2 = “240 Seconds”
3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”
0
A187 [Bus Reg Mode]
0/1
0 = “Disabled”
1 = “Enabled”
1
No.
Parameter
Min/Max
Display/Options
Default