background image

Rockwell Automation Publication 1734-IN032F-EN-P - September 2022

3

POINT I/O 4 Channel High Density Current Input Module Installation Instructions

Environment and Enclosure

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 

60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such 

environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific 

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure 

must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the 

application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more 

information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publicatio

1770-4.1

, for more installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

Preventing Electrostatic Discharge

ATTENTION: 

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines 

when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wrist strap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous 

locations.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 

Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is 

supplied with markings on the rating nameplate indicating the hazardous location 

temperature code. When combining products within a system, the most adverse 

temperature code (lowest "T" number) may be used to help determine the overall 

temperature code of the system. Combinations of equipment in your system are subject 

to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en 

environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. 

Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent 

le code de température pour les environnements dangereux. Lorsque plusieurs produits 

sont combinés dans un système, le code de température le plus défavorable (code de 

température le plus faible) peut être utilisé pour déterminer le code de température 

global du système. Les combinaisons d'équipements dans le système sont sujettes à 

inspection par les autorités locales qualifiées au moment de l'installation.

WARNING:

Explosion Hazard –

• Do not disconnect equipment unless power has been removed or 

the area is known to be nonhazardous. 

• Do not disconnect connections to this equipment unless power has 

been removed or the area is known to be nonhazardous. Secure 

any external connections that mate to this equipment by using 

screws, sliding latches, threaded connectors, or other means 

provided with this product.

• Substitution of components may impair suitability for Class I, 

Division 2.

AVERTISSEMENT:

Risque d’Explosion – 

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non 

dangereux avant de débrancher les connecteurs. Fixer tous les 

connecteurs externes reliés à cet équipement à l'aide de vis, 

loquets coulissants, connecteurs filetés ou autres moyens fournis 

avec ce produit.

• La substitution de composants peut rendre cet équipement 

inadapté à une utilisation en environnement de Classe I, Division 2.

ATTENTION: 

To comply with UL restrictions, field power and all connected devices must be powered from a single source compliant with the following: Class 2

ATTENTION: 

To comply with the CE Low Voltage Directive (LVD), field power and all connected I/O must be powered from a source compliant with the following: 

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

Summary of Contents for Allen-Bradley POINT I/O 1734-IE4C

Page 1: ...ubstantive updates only and is not intended to reflect all changes Topic Page Summary of Changes 1 Before You Begin 5 Install the Mounting Base 6 Install the Module 7 Install the Removable Terminal Bl...

Page 2: ...ocumento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzion...

Page 3: ...are suitable for use in Class I Division 2 Groups A B C D Hazardous Locations and nonhazardous locations only Each product is supplied with markings on the rating nameplate indicating the hazardous l...

Page 4: ...numbers followed by a K to indicate a conformal coating option IEC Hazardous Location Approval The following applies to products with IECEx certification Are intended for use in areas in which explos...

Page 5: ...e of the following 1734 TB or 1734 TBS POINT I O two piece terminal base which includes the 1734 RTB removable terminal block and 1734 MB mounting base 1734 TOP or 1734 TOPS POINT I O one piece termin...

Page 6: ...locking screw to a vertical position This releases the locking mechanism Then lift straight up to remove Description Description 1 Module locking mechanism 6 Interlocking side pieces 2 Slide in writab...

Page 7: ...the Removable Terminal Block proceed as follows 1 Insert the end opposite the handle into the base unit This end has a curved section that engages with the wiring base 2 Rotate the terminal block into...

Page 8: ...2 Slide the base down allowing the interlocking side pieces to engage the adjacent installed unit 3 Press firmly to seat the base on the DIN rail until the base snaps into place 4 Verify that the DIN...

Page 9: ...wiring while the field side power is on an electric arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before pro...

Page 10: ...hannel 3 High Byte Input Channel 3 Low Byte Status Byte for Channel 1 Status Byte for Channel 0 OR UR HHA LLA HA LA CM CF OR UR HHA LLA HA LA CM CF Status Byte for Channel 3 Status Byte for Channel 2...

Page 11: ...hing green Channel being calibrated Solid red No power or major channel fault Flashing red Channel at end of range 0 mA or 21 mA IMPORTANT The Input update rate and Step response for 1734 IE4C and 173...

Page 12: ...nal base 1734 TB3 1734 TB3S wiring base assembly POINTBus current max 75 mA Power dissipation max 0 55 W 28 8V DC Thermal dissipation max 2 0 BTU hr 28 8V DC Supply voltage backplane 5V DC Supply volt...

Page 13: ...e line DM and 2 kV line earth CM on power ports 2 kV line earth CM on shielded ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM 150 kHz 80 MHz Certifications Certification...

Page 14: ...nt with Article 58 2 of Radio Waves Act Clause 3 Morocco Arr t minist riel n 6404 15 du 29 ramadan 1436 CCC CNCA C23 01 CNCA C23 01 CCC Implementation Rule Explosion Proof Electrical Products CCC 2020...

Page 15: ...Rockwell Automation Publication 1734 IN032F EN P September 2022 15 POINT I O 4 Channel High Density Current Input Module Installation Instructions Notes...

Page 16: ...equipment should be collected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us s...