24
Rockwell Automation Publication MM-IN001B-EN-P - February 2022
Kinetix MMA Asynchronous Main Motors Installation Instructions
Brake Terminations
.
The brake configuration and option for each motor varies. The standard motor
configuration is to have no brake. The brake can be fitted with a microswitch to
monitor brake status release or engagement. The microswitch can be wired on the
motor terminal strip as a normally closed contact or a normally open contact. The
brake microswitch leads must be landed on the motor terminal strip.
The deceleration/braking of the system must be done dynamically through the
inverter. The holding brake is only suitable to keep the shaft locked during cycle
pauses and to be activated when the motor has stopped turning. Do not repeatedly
use the brake during the machine cycle or to reduce the deceleration time of the
system.
Table 16 - Thermal Sensors and Thermal Switch Specifications
Description
TS
(1)
KTY 84-130, PT100, or PT1000
(2)
Terminal Board Layout
Type of protection
Slow overload, insufficient ventilation Temperature monitoring
Temperature measure
No
Yes
Type of signal
Normally closed contact
Linear variable resistance
Intervention temperature
150 °C (302 °F)
—
Resistance at 20 °C (68 °F)
< 1 Ω
See
Resistance at the intervention temperature
< 1 Ω
See
Resistance after the intervention
∞
See
Rated supply voltage
110V AC
—
Maximum supply voltage
250V AC / 60V DC
—
Maximum current
AC = 2.5 A / DC = 1 A
2 mA
Reset temperature
85…95 °C (185…203 °F)
—
(1)
The TS is the thermostat.
(2)
Resistive temperature device (RTD).
Table 17 - Thermal Sensor Temperature and Resistance Values
Temperature °C (°F)
PT100 Ω
PT1000 Ω
KTY 84-130 Ω
Temperature °C (°F)
PT100 Ω
PT1000 Ω
KTY 84-130 Ω
-20 (-4)
92.16
921
419
80 (176)
130.89
1309
880
-10 (14)
96.09
960
455
90 (194)
134.70
1347
939
0 (32)
100.00
1000
493
100 (212)
138.50
1385
1000
10 (50)
103.90
1039
533
110 (230)
142.29
1423
1063
20 (68)
107.79
1078
576
120 (248)
146.06
1461
1129
30 (86)
111.67
1117
621
130 (266)
149.82
1498
1198
40 (104)
115.54
1155
668
140 (284)
153.58
1536
1268
50 (122)
119.40
1194
718
150 (302)
157.31
1573
1340
60 (140)
123.24
1232
769
160 (320)
161.04
1610
1415
70 (158)
127.07
1271
824
170 (338)
164.76
1647
1493
180 (356)
168.46
1685
1572
TS 150 °C
(302 °F)
PT 1000
windings
KTY 84-130
—
+
TS (Thermal Switch)
I [A]
T [°C]
TNF
KTY – PT100 – PT1000
R [Ω]
T [°C ]
Microswitch
Brake
24V DC
N.O.
COM
N.C.
Brake
400V DC
Microswitch
N.O.
COM
N.C.