Summary of Contents for Allen-Bradley CompactLogix 1769-L32E

Page 1: ...ll a 1784 CF64 or 1784 CF128 CompactFlash Card optional 8 Assemble the System 9 Mount the System 11 Make RS 232 Connections to the Controller 15 Make Ethernet Connections to the Controller 18 Load the Controller Firmware 25 Select the Controller s Operating Mode 29 Controller Status Indicators 31 RS 232 Serial Port Status Indicators Channel 0 33 CompactFlash Card Status Indicator 33 Module Status ...

Page 2: ...stallation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is pro...

Page 3: ...vent or minimize the spread of flame complying with a flame spread rating of 5VA V2 V1 V0 or equivalent if non metallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications In addition to th...

Page 4: ... plus défavorable code de température le plus faible peut être utilisé pour déterminer le code de température global du système Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not dis...

Page 5: ... intended for use in potentially explosive atmospheres given in Annex II to this Directive Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079 15 and EN 60079 0 WARNING This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments This equipment shall be used within its specified ratings...

Page 6: ...any as 30 I O modules Both controllers can use a maximum of 3 I O banks with 2 expansion cables Each I O bank requires its own power supply Only one controller can be used in a CompactLogix system A 1769 ECR right end cap or 1769 ECL left end cap is required to terminate the end of the communication bus Parts List These components ship with the controller You may also use these components with the...

Page 7: ...ttery you can use with the 1769 L32E and 1769 L35E controllers The 1747 BA battery is not compatible with the 1769 L32E and 1769 L35E controllers and may cause problems WARNING When you connect or disconnect the battery an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding For safety...

Page 8: ...hould be collected separately from any unsorted municipal waste and recycled ATTENTION Do not remove the CompactFlash card while the controller is reading from or writing to the card as indicated by a flashing green CF status indicator This could corrupt the data on the card or in the controller as well as corrupt the latest firmware in the controller WARNING When you insert or remove the CompactF...

Page 9: ...ard push the locking tab away from the CompactFlash card and pull the CompactFlash card from the socket Assemble the System The controller can be attached to an adjacent I O module or power supply before or after mounting For mounting instructions see Ground the Wiring on page 12 or Mount the Panel on page 13 WARNING The CompactLogix controller is not designed for removal and insertion under power...

Page 10: ... the tongue and groove slots until the bus connectors line up with each other 5 Use your fingers or a small screwdriver to push the module s bus lever back slightly to clear the positioning tab C 6 Move the module s bus lever fully to the left D until it clicks being sure it is locked firmly in place ATTENTION When attaching the controller power supply and I O modules make sure the bus connectors ...

Page 11: ...and adjacent equipment Allow 50 mm 2 in of space on all sides as shown This provides ventilation and electrical isolation ATTENTION During panel or DIN rail mounting of all devices be sure that all debris such as metal chips or wire strands is kept from falling into the controller Debris that falls into the controller could cause damage while the controller is energized Bottom Side Side Top Compac...

Page 12: ...ompact I O expansion cables have the same dimensions as the end caps Expansion cables can be used on either the right or left end A 1769 ECR right end cap or 1769 ECL left end cap terminates the end of the communication bus ATTENTION This product is grounded through the DIN rail to chassis ground Use zinc plated yellow chromate steel DIN rail to assure proper grounding The use of other DIN rail ma...

Page 13: ...modules to the clean work surface including any previously mounted modules 4 Drill and tap the mounting holes for the recommended M4 or 8 screw 5 Place the modules back on the panel and check for proper hole alignment 6 Attach the modules to the panel by using the mounting screws 7 Repeat steps 1 6 for any remaining modules IMPORTANT Due to module mounting hole tolerance it is important to follow ...

Page 14: ...s the DIN rail mounting area of the controller against the DIN rail The latches will momentarily open and lock into place ATTENTION This product is grounded through the DIN rail to chassis ground Use zinc plated yellow chromate steel DIN rail to assure proper grounding The use of other DIN rail materials for example aluminum or plastic that can corrode oxidize or are poor conductors can result in ...

Page 15: ...erial device on the other end of the cable an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding TIP This cable must be shielded and tied to the connector housing 44735 2 RDX 3 TXD 4 DTR COMMON 6 DSR 7 RTS 8 CTS 9 1 CD 2 RDX 3 TXD 4 DTR COMMON 6 DSR 7 RTS 8 CTS 9 1 CD 1747 CP3 or 175...

Page 16: ...Parameter Default Protocol DF1 full duplex Communication Rate 19 2 Kbps Parity None Station Address 0 Control Lines No Handshaking Error Detection BCC Embedded Responses Auto Detect Duplicate Packet Message Detect Enabled ACK Timeout 50 x 20 ms NAK Receive Limit 3 Retries ENQ Transmit Limit 3 Retries Data Bits 8 Stop Bits 1 TIP Only Channel 0 has a default communication push button see page 17 ...

Page 17: ... to indicate that the default communication configuration is active TIP The default communication push button is recessed Before pressing the default communication push button be sure to note the present communication configuration for Channel 0 Pushing the default communication push button resets all configured parameters to their default settings To return the channel to its user configured para...

Page 18: ... the Ethernet cable to the Ethernet port top port on the controller WARNING If you connect or disconnect the communications cable with power applied to this module or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding ATTENTION Do not plug a DH 485 networ...

Page 19: ...tware Use BOOTP to Set the IP Address The BOOTP utility is a standalone program in one of the following directories RSLinx Tools directory in the Rockwell Software program folder on the Start menu the utility is automatically installed when you install RSLinx software Utils directory on the RSLogix 5000 software installation CD Follow this procedure to use the BOOTP utility 1 Start the BOOTP softw...

Page 20: ...ses of devices issuing BOOTP requests 5 Double click the hardware address of the device you want to configure TIP The hardware address is on the sticker on the left side circuit board of the controller next to the battery See Connect the 1769 BA Battery on page 7 for instructions on accessing this area The hardware address will be in this format 00 0b db 14 55 35 ...

Page 21: ...ght the device and click Disable BOOTP DHCP When power is recycled the device uses the configuration you assigned and does not issue a BOOTP request Use RSLinx Software to Set the IP Address You can use RSLinx software version 2 41 or later to set the IP address 1 Make sure the controller that uses the IP address is installed and running 2 Connect to the controller via the serial connection see pa...

Page 22: ...gix Controller Publication 1769 IN020D EN P October 2008 4 Navigate to the Ethernet network via the Serial network 5 Right click the Ethernet port not the controller and select Module Configuration 6 Select the Port Configuration tab ...

Page 23: ...ration type 8 Enter the IP address network subnet mask and gateway address if needed Use RSLogix 5000 Software to Set the IP Address You can use RSLogix software to set the IP address 1 Make sure the controller that uses the IP address is installed and running 2 Connect to the controller via the serial connection see page 15 3 Start RSLogix 5000 software ...

Page 24: ...r 2008 4 In the Controller Organizer select properties for the Ethernet port 5 Choose the Port Configuration tab 6 Specify the IP address 7 Click Apply 8 Click OK This sets the IP address in the hardware This IP address should be the same IP address you assigned under the General tab ...

Page 25: ...evision 1 EDS file 0001000E00410100 eds installed for the controller The EDS files are available on the RSLogix 5000 Enterprise Series software CD The files are also available at http www ab com networks eds Load the Controller Firmware You must download the current firmware before you can use the controller To load firmware you can use any of the following ControlFlash utility that ships with RSL...

Page 26: ... data Use the ControlFlash Utility to Load Firmware You can use the ControlFlash utility to load firmware through a serial connection 1 Make sure the appropriate network connection is made before starting 2 Start the ControlFlash utility 3 When the Welcome dialog appears click Next 4 Choose the catalog number of the controller and click Next 5 Expand the network until you see the controller 6 If t...

Page 27: ...amming software to create a controller project 3 Click RSWho to specify the controller path 4 Select your controller and click Download You may also choose to click Update Firmware to complete this process If you do so skip to step 8 A dialog box displays indicating that the project revision and controller firmware revision are different IMPORTANT When upgrading your controller firmware it is extr...

Page 28: ...u have an existing controller that is already configured and has firmware loaded you can store the current controller user program and firmware on the CompactFlash card and use that card to update other controllers 1 Use RSLogix 5000 software to store the controller user program and firmware of a currently configured controller to the CompactFlash card 2 Access the Nonvolatile Memory tab of the Co...

Page 29: ...s operating mode Keyswitch Position Description Run Upload projects Run the program and enable outputs You cannot create or delete tasks programs or routines You cannot create or delete tags or edit online while the keyswitch is in the Run position You cannot change the mode by using the programming software while the keyswitch is in the Run position Prog Disable outputs Upload download projects C...

Page 30: ...mote Run modes through the programming software Remote Run The controller executes scans tasks Enable outputs Edit online Remote Program Disable outputs Create modify and delete tasks programs or routines Download projects Edit online The controller does not execute scan tasks Remote Test Execute tasks with outputs disabled Edit online Keyswitch Position Description ...

Page 31: ...e input or output addresses have been forced to an On or Off state but the forces have not been enabled BAT Off The battery supports memory Solid red Either the battery is not installed 95 discharged and should be replaced I O Off Either There are no devices in the I O configuration of the controller The controller does not contain a project controller memory is empty Solid green The controller is...

Page 32: ... Prog to Run to Prog Go online with RSLogix 5000 software Solid red The controller detected a nonrecoverable fault so it cleared the project from memory Cycle power to the chassis When the controller is ready download the project and change to RUN mode If the OK status indicator remains solid red contact your Rockwell Automation representative or local distributor Solid green Controller is OK Flas...

Page 33: ...ing to the card as indicated by a flashing green CF status indicator This could corrupt the data on the card or in the controller as well as corrupt the latest firmware in the controller Indicator Status Description CF Off No activity Flashing green The controller is reading from or writing to the CompactFlash card Flashing red CompactFlash card does not have a valid file system Condition Status D...

Page 34: ...etwork Updating firmware The controller firmware is being updated Normal operation during firmware update No action required Condition Status Description Off No IP address The controller does not have an IP address and is operating in BOOTP mode Verify the BOOTP server is running Flashing green No CIP connections established The controller has an IP address but no CIP connections are established I...

Page 35: ...e controller cannot communicate on Ethernet Verify that all Ethernet cables are connected Verify that Ethernet switch is powered Flashing green Self test The controller is performing its power up self test Normal operation No action required Data transmission and reception The controller is communicating on Ethernet Normal operation No action required Solid green Link OK The port is connected to a...

Page 36: ...er of I O modules max 16 I O modules 30 I O modules Number of I O banks max 3 banks Backplane current 660 mA at 5V DC 90 mA at 25 V DC Power consumption 5 5 W Power dissipation 5 5 W Power supply distance rating 4 The controller must be within four slot positions of the power supply Isolation voltage 30V continuous Basic Insulation Type Type tested at 710V dc for 60 s RS232 to system ENET to syste...

Page 37: ...Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 1769 L32E 1769 L35E Environmental Specifications Attribute 1769 L32E 1769 L35E Operating temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 60 C 32 140 F Nonoperating temperatu...

Page 38: ...11 Group 1 Class A ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 10V m with 1 kHz sine wave 80 AM from 30 2000 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on communication ports Surge transient i...

Page 39: ... EC EMCDirective compliant with EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions C Tick Australian Radio Communications Act complaint with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n II 3 G Ex nA IIC T4 X EN 60079 0 General Requirements Zone 2 EtherNet IP ODVA conformance t...

Page 40: ...res publication 1756 PM001 Developing projects for Logix5000 controllers Logix5000 Controllers General Instructions Reference Manual publication 1756 RM003 Programming the controller for sequential applications Logix5000 Controllers Process Control and Drives Instructions Reference Manual publication 1756 RM006 Programming the controller for process or drives applications CompactLogix System User ...

Reviews: