Rockwell Automation Publication 1512A-UM101B-EN-P - December 2021
91
Appendix
C
ArcShield Chimney Installation Instructions
The following instructions are provided to ensure the proper installation and
function of chimney supplied with ArcShield™ enclosures. Refer to
for additional information related to ArcShield chimney before attempting to
follow these instructions.
Recommended Torque
Values
1 /4 -20 Thread Fasteners — 15 N•m (12 lb•ft)
5 /16 -18 Thread Fasteners — 14.5 N•m (11 lb•ft)
Figure 78 - Chimney Exhaust Label
IMPORTANT
Plan the location where the plenum will exhaust (refer to
). The plenum exhaust area is to be marked as a
Hazardous Zone, and labeled per
.
ARC FLASH HAZARD
PRESSURE RELIEF EXIT
AREAS TO BE:
- INACCESSIBLE TO PERSONNEL
WHILE EQUIPMENT ENERGIZED.
- FREE OF OBSTRUCTIONS
(REFER TO USER MANUAL).
SEVERE INJURY OR
DEATH MAY RESULT.
SORTIE DE L’ÉVENT
RÉGION ÊTRE:
- INACCESSIBLE AUX PERSONNEL
PENDANT QUE L’ÉQUIPEMENT
EST SOUS TENSION.
- DÉMUNI D’OBSTRUCTIONS
(RÉFÉRER AU MANUEL)
RISQUE DE BLESSURES
CORPORELLES GRAVES
OU MÊME LA MORT.
DANGER
DANGER
HAZARD D’ARC ÉLECTRIQUE