62
Rockwell Automation Publication 7712-UM001D-EN-P - October 2017
Appendix B
Certification Data
Table 11 - Test reports verifying ratings assigned by the manufacturer:
Performances
Test According to Standard/Clause
Test Reports
Number
Issued By
Dielectric Tests
Power frequency withstand 20 kV/1 min
20969-B-26
07/06/2011
20969-B-26
07/06/2011
Powertech
Impulse 15± 60 kV/1.2/50 µs
ER-059-2012
Rockwell Automation
LV control 2 kV/1 min
IEC 82271-1/6.2.10
ER-004-2012
Rockwell Automation
Measurement of Circuit Resistance
IEC 60470/6.4, IEC 62271-1/6.4
20969-B-26, 07/06/2011
Powertech
Temperature Rise Test
7712 Starter 250 A
IEC 60470/6.5, IEC62271-1/6.5, Table 3
11071-C, 03/29 - 31/2011
KEMA
Verification of operating limits
+10%, -15% LV control
IEC 6470/6.101.1
20969-A-26
07/06/2011
Powertech
Short-time and peak withstand tests
Main bus 50 kA/3 s
IEC 60470/6.6
IEC 6227101/6.6.2
IEC 562271-200/
11069-B 03/28/2011
KEMA
Ground bus 60 kA/3 s
20158-1 08/16-18/2010
Powertech
Vertical bus 50 kA/0.3 s
20969-D-26 07/08/2011
Powertech
Earthing switch 31.5 kA/
IEC 62271-102/6.101
IEC 62271-200/6.6b
EP-2485R
Rockwell Automation (HCL)
Mechanical Operation Tests
Earthswitch and starter 50CO
IEC 6470/6.101.2
ER-069-2012
Rockwell Automation
Interlock 25CO
IEC 6470/6.101.3
ER-069-2012
Rockwell Automation
Earthswitch Class M1 2000 CO
IEC 62271-102/4.106, 6.102
ER-110-2011
Rockwell Automation
Overload Current Tests
6 kA/1 s
IEC 6470/6.102.7
20969-B-26
07/06/2011
Powertech
2.4 kA/30 s
Rated making and breaking capacity tests AC4
Fused starter making 4 kA/100C Table 10,
12 kV TRV
IEC 62271-1/6.102.4
20969-A-26
07/06/2011
Powertech
Fused starter breaking 3.2k25O, 80 A/25O,
Table 10, 12kV TRV
IEC 62271-1/6.102.5
20969-A-26
07/06/2011
Short-circuit making and breaking tests
Starter Make/Break 1CO at 6.1 kA
IEC60470/6.104
20969-E-26
07/08/2011
Powertech
Earthing Switch Making
5 x C @ 31.5 kA Peak
IEC 60265, 6.107.1
EP-2485R
Rockwell Automation (HCL)
SCPD Coordination
Type A -40kArms 1O (fused)
IEC60470/6.106.3.1
20969-C-26
07/07/2011
Powertech
Type B 40kArms 1CO (fused)
IEC60470/6.106.3.2
Type C 5.1kArms 3CO (unfused)
IEC60470/6.106.3.3
Degree of Protection
External surface IP4X
IEC 60470/5/13
IEC 62271-1/5.13
ER-070-2012
Rockwell Automation
Internal barriers IP2X
ER-070-2012
Rockwell Automation
Arc Tests
7712 Starter 31.5 kA/0.5 s line side
IEC 62271-200/ Annex A, AFLR
20158-2, 08/16-18/2010
Powertech
Summary of Contents for Allen-Bradley 7712
Page 6: ...6 Rockwell Automation Publication 7712 UM001D EN P October 2017 Table of Contents Notes ...
Page 10: ...10 Rockwell Automation Publication 7712 UM001D EN P October 2017 Preface Notes ...
Page 24: ...24 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Page 25: ...Rockwell Automation Publication 7712 UM001D EN P October 2017 25 Start up Procedure Chapter 3 ...
Page 26: ...26 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 3 Start up Procedure ...
Page 58: ...58 Rockwell Automation Publication 7712 UM001D EN P October 2017 Chapter 5 Maintenance Notes ...
Page 73: ......