Rockwell Automation Publication 7712-UM001D-EN-P - October 2017
57
Maintenance
Chapter 5
Vertical Adjustment
1. Loosen the two tapties that mount the L-bracket to the base.
2. Move the L-bracket up and down as required.
3. Secure the adjusted position of auxiliary by tightening the two M6
taptie.
Figure 42 - Auxiliary Contacts Adjustment
Earthing Switch Auxiliary Contacts Inspection
Operation of electrical auxiliaries must be validated on a yearly basis.
Refer to the unit electrical drawing to determine the test locations on the
terminals located in the low voltage compartment.
IMPORTANT
Auxiliaries must be tested electrically with control power off.