Kinetix 350 Single-axis EtherNet/IP Servo Drives
5
Rockwell Automation Publication 2097-IN008B-EN-P - October 2011
Mount the Kinetix 350 Drive
Follow these steps to mount the drive.
1.
Observe these clearance requirements when mounting the drive to the panel. .
IMPORTANT
Mount the module in an upright position as shown. Do not mount the module on
its side.
Drive
Cat. No.
Dimensions A
mm (in.)
2097-V31PR0-LM
185 (7.29)
2097-V31PR2-LM
2097-V32PR0-LM
230 (9.04)
2097-V32PR2-LM
2097-V32PR4-LM
2097-V33PR1-LM
185 (7.29)
(1)
(1) If using an AC line filter, add 50 mm (2
in.).
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM
230 (9.04)
2097-V34PR3-LM
185 (7.29)
2097-V34PR5-LM
2097-V34PR6-LM
230 (9.04)
A
25 mm (1.0 in.) Clearance
for Airflow and Installation
25 mm (1.0 in.) Clearance
for Airflow and Installation
3 mm (0.12 in.)
Side Clearance
3 mm (0.12 in.)
Side Clearance
•
Additional clearance and different hole patterns are required for side
mount and rear mount AC line filters. See the table and step
for more
details.
•
Additional clearance is required depending on the other accessory
items installed.
•
Additional clearance is required for the cable and wires connected to
the top, front, and bottom of the drive.
•
Additional 150 mm (6.0 in.) is required when the drive is mounted
adjacent to noise sensitive equipment or clean wire ways.
Refer to page
for Kinetix 350 drive dimensions.