Rockwell Automation Allen-Bradley 1606-XLDF240F Reference Manual Download Page 6

6

Rockwell Automation Publication 1606-RM124A-EN-P - September 2021

DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual

Specifications

Catalog Numbers

DC Input

The input can be powered from batteries or similar DC sources. To maintain a 
SELV or PELV output, the source must be a PELV or SELV source, or an 
Isolated Secondary Circuit.

Check for correct input polarity. The device does not operate when the voltage 
is reversed.

Attributes

Values

Notes

Output voltage nom

DC 48V

Adjustment range

48…56V

Factory setting 48.0V

Output current

6…5.2 A

5…4.3 A

3.8…3.2 A

Below 45 °C (113 °F) ambient

At 60 °C (140 °F) ambient

At 70 °C (158 °F) ambient

Derate linearly between 45…70 °C (113…158 °F)

Input voltage DC

48V

±25%

Input current

5.3 A 

Input inrush current

7 A peak

Efficiency

95.1% 

Losses

12.4 W

Hold-up time

7.7 ms

Temperature range

-25…+70 °C (-13…+158 °F)

Size (W x H x D)

42 x 124 x 117 mm (1.65 x 4.88 x 4.61 in.)

Without DIN rail

Weight

500 g (1.1 lb)

Catalog Numbers Description

1606-XLDF240F

DC/DC converter

1606-XLC

Wall or panel mount bracket; see 

page 17

1606-XLA-S44

Side mount bracket; see 

page 17

Attributes

Values

Notes

DC input

Nom

48V

±25%

DC input range

Min

36…60V DC

Continuous operation

Allowed voltage L or N to 

earth

Max

60V DC or 42.2V 

AC

Continuous according to IEC 62477-1

.

Allowed input ripple voltage Max

10 Vpp

In the frequency range from 47…500Hz, the momentary 

input voltage must always be within the specified limits.

Turn-on voltage

Typ

35V DC

Steady-state value; see 

Figure 1 on page 7

.

Shut-down voltage

Typ

31V DC

Steady-state value; see 

Figure 1 on page 7

.

Input current

Typ

5.3 A

At 48V DC input and 48V, 5 A output load; see 

Figure 3 on 

page 7

.

7 A

At 36V DC input and 48V, 5 A output load; see 

Figure 3 on 

page 7

.

Startup delay

Typ

350 ms

See 

Figure 1 on page 7

.

Rise time

Typ

50 ms

At 48V, 5 A constant current load, 0 mF load capacitance; 

see 

Figure 2 on page 7

.

150 ms

At 48V, 5 A constant current load, 5 mF load capacitance; 

see 

Figure 2 on page 7

.

Summary of Contents for Allen-Bradley 1606-XLDF240F

Page 1: ...DC DC Converter 48V 48V 5 A 240 W Catalog Number 1606 XLDF240F Reference Manual Original Instructions...

Page 2: ...ell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission...

Page 3: ...romagnetic Compatibility 13 Environment 14 Safety and Protection Features 15 Dielectric Strength 15 Approved Fulfilled or Tested Standards 16 Regulatory Product Compliance 16 Physical Dimensions and W...

Page 4: ...4 Rockwell Automation Publication 1606 RM124A EN P September 2021 Table of Contents Notes...

Page 5: ...DC output Efficiency up to 95 1 Width only 42 mm 1 65 in 20 output power reserves Full power between 25 60 C 13 140 F Soft start function Minimal inrush current surge Reverse input polarity protection...

Page 6: ...x 4 88 x 4 61 in Without DIN rail Weight 500 g 1 1 lb Catalog Numbers Description 1606 XLDF240F DC DC converter 1606 XLC Wall or panel mount bracket see page 17 1606 XLA S44 Side mount bracket see pag...

Page 7: ...led inside the device external capacitors on the input are allowed without any limitations External input protection The device is designed tested and approved for branch circuits up to 50 A without a...

Page 8: ...his function increases the rise time of the output voltage by a small amount Output The output provides a SELV PELV rated voltage which is galvanically isolated from the input voltage and is designed...

Page 9: ...t current Max 7 A Continuous current short circuit impedance 90 m Output capacitance Typ 1750 F Included inside the power supply Back feeding loads Max 63V The unit is resistant and does not show malf...

Page 10: ...A 94 9 At 48V 6 A power boost Average efficiency Typ 94 6 25 at 1 25 A 25 at 2 5 A 25 at 3 75 A 25 at 5 A Power losses Typ 2 1 W At no output load 6 7 W At 48V 2 5 A 12 4 W At 48V 5 A 15 5 W At 48V 6...

Page 11: ...inals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output 2 Output voltage potentiometer Open the flap to set t...

Page 12: ...tical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product An MTBF value of for example 1 000 000 hr means that statistically one unit fails ever...

Page 13: ...discharge 8 kV Criterion A Air discharge 15 kV Criterion A Electromagnetic RF field EN 61000 4 3 80 MHz 2 7 GHz 20V m Criterion A Fast transients Burst EN 61000 4 4 Input lines 4 kV Criterion A Outpu...

Page 14: ...1 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm 0 59 in and a thickness of 1 3 mm 0 05 in These tests are performed with the DC DC converter...

Page 15: ...input and PE measured with 500V DC Min 500 M At delivered condition between output and PE measured with 500V DC PE resistance Max 0 1 Resistance between PE terminal and the housing in the area of the...

Page 16: ...he Council of June 1 2007 regarding the Registration Evaluation Authorization and Restriction of Chemicals REACH Ind Cont Eq Attributes Values and Descriptions Width 42 mm 1 65 in Height 124 mm 4 88 i...

Page 17: ...ins the two brackets that are needed for one device Figure 22 Cat No 1606 XLC Wall Panel Mount Bracket Side Mount Bracket Cat No 1606 XLA S44 This bracket mounts the device sideways with or without us...

Page 18: ...the perfect choice when the power supply has no DC OK function Two light emitting diode LEDs and two relay contacts signal when one of the two input voltages is not in range due to a non functioning...

Page 19: ...discharged during such an event which causes a voltage dip on the output Figure 24 and Figure 25 show two typical voltage dips Output Circuit Breakers Standard miniature circuit breakers MCB s or UL 1...

Page 20: ...DC must be installed with protection against touching Avoid return voltage for example from a decelerating motor or battery that is applied to the output terminals Keep a left right installation clea...

Page 21: ...Redundancy Devices can be paralleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The si...

Page 22: ...ide of the DC DC converter with a distance of 1 cm 0 39 in The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure Figure 26 1 1 Redundant Co...

Page 23: ...28 Mounting Orientation A upright standard Figure 29 Mounting Orientation B upside down Figure 30 Mounting Orientation C table top Figure 31 Mounting Orientation D horizontal with input on the left Fi...

Page 24: ...24 Rockwell Automation Publication 1606 RM124A EN P September 2021 DC DC Converter 48V 48V 5 A 240 W Reference Manual Notes...

Page 25: ...closures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application I...

Page 26: ...edgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installat...