Rockwell Automation Allen-Bradley 1606-XLDF240F Reference Manual Download Page 21

Rockwell Automation Publication 1606-RM124A-EN-P - September 2021

21

DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual

Parallel Use to Increase 

Output Power

Devices can be connected paralleled to increase the output power. You can 
adjust the output voltage to the same value (±100 mV) with the same load 
conditions on all devices, or the devices can be left with the factory settings.

The ambient temperature cannot exceed 
45 °C (113 °F).

If more than three devices are connected 
in parallel, a fuse or circuit breaker with 
a rating of 10 A is required on each 
output. A diode or redundancy module 
can also be used.

Keep a left/right installation clearance of 
15 mm (0.6 in.) between two power 
supplies. Do not install the power 
supplies on top of each other. Do not use devices in parallel in mounting 
orientations other than the standard mounting orientation, or in any other 
condition where a reduction of the output current is required (for example, 
altitude).

EMI and inrush current increase when you use multiple devices.

Parallel Use for Redundancy

These devices can be parallel used for two types of redundancy. For a wiring 
example of either redundancy configuration, see 

Figure 26

 and 

Figure 27

, both 

on 

page 22

.

1+1 Redundancy

Devices can be paralleled for 1+1 redundancy to gain higher system availability. 
Redundant systems require a certain amount of extra power to support the 
load in case one device fails. The simplest way is to put two devices in parallel. 
This is called a 1+1 redundancy. In case one device fails, the other one is 
automatically able to support the load current without any interruption. It is 
essential to use a redundancy module to decouple devices from each other. 
This redundancy helps prevent the defective unit from becoming a load for the 
other device, which helps confirm that the output voltage can be maintained.

EMI and inrush current increase when you use multiple devices.

The following recommendations are for building 1+1 redundant power systems:

Whenever possible, use separate supply systems for each device.

Monitor the outputs of each device. Use the DC-OK lamp or the DC-OK 
contact, which are included in the Cat. No. 1606-XLERED Redundancy 
Module.

Set the output voltages of all devices to the same value (± 100 mV), or 
leave them at the factory setting.

The ambient temperature cannot exceed 70 °C (158 °F).

N+1 Redundancy

Redundant systems for a higher power demand are built in an N+1 method, 
such as four devices with each rated for 10 A are paralleled to build a 30 A 
redundant system.

EMI and inrush current increase when you use multiple devices.

Unit A

Input

Output

Unit B

Input

Output

-

+

-

+

+

-

Load

Summary of Contents for Allen-Bradley 1606-XLDF240F

Page 1: ...DC DC Converter 48V 48V 5 A 240 W Catalog Number 1606 XLDF240F Reference Manual Original Instructions...

Page 2: ...ell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission...

Page 3: ...romagnetic Compatibility 13 Environment 14 Safety and Protection Features 15 Dielectric Strength 15 Approved Fulfilled or Tested Standards 16 Regulatory Product Compliance 16 Physical Dimensions and W...

Page 4: ...4 Rockwell Automation Publication 1606 RM124A EN P September 2021 Table of Contents Notes...

Page 5: ...DC output Efficiency up to 95 1 Width only 42 mm 1 65 in 20 output power reserves Full power between 25 60 C 13 140 F Soft start function Minimal inrush current surge Reverse input polarity protection...

Page 6: ...x 4 88 x 4 61 in Without DIN rail Weight 500 g 1 1 lb Catalog Numbers Description 1606 XLDF240F DC DC converter 1606 XLC Wall or panel mount bracket see page 17 1606 XLA S44 Side mount bracket see pag...

Page 7: ...led inside the device external capacitors on the input are allowed without any limitations External input protection The device is designed tested and approved for branch circuits up to 50 A without a...

Page 8: ...his function increases the rise time of the output voltage by a small amount Output The output provides a SELV PELV rated voltage which is galvanically isolated from the input voltage and is designed...

Page 9: ...t current Max 7 A Continuous current short circuit impedance 90 m Output capacitance Typ 1750 F Included inside the power supply Back feeding loads Max 63V The unit is resistant and does not show malf...

Page 10: ...A 94 9 At 48V 6 A power boost Average efficiency Typ 94 6 25 at 1 25 A 25 at 2 5 A 25 at 3 75 A 25 at 5 A Power losses Typ 2 1 W At no output load 6 7 W At 48V 2 5 A 12 4 W At 48V 5 A 15 5 W At 48V 6...

Page 11: ...inals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output 2 Output voltage potentiometer Open the flap to set t...

Page 12: ...tical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product An MTBF value of for example 1 000 000 hr means that statistically one unit fails ever...

Page 13: ...discharge 8 kV Criterion A Air discharge 15 kV Criterion A Electromagnetic RF field EN 61000 4 3 80 MHz 2 7 GHz 20V m Criterion A Fast transients Burst EN 61000 4 4 Input lines 4 kV Criterion A Outpu...

Page 14: ...1 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm 0 59 in and a thickness of 1 3 mm 0 05 in These tests are performed with the DC DC converter...

Page 15: ...input and PE measured with 500V DC Min 500 M At delivered condition between output and PE measured with 500V DC PE resistance Max 0 1 Resistance between PE terminal and the housing in the area of the...

Page 16: ...he Council of June 1 2007 regarding the Registration Evaluation Authorization and Restriction of Chemicals REACH Ind Cont Eq Attributes Values and Descriptions Width 42 mm 1 65 in Height 124 mm 4 88 i...

Page 17: ...ins the two brackets that are needed for one device Figure 22 Cat No 1606 XLC Wall Panel Mount Bracket Side Mount Bracket Cat No 1606 XLA S44 This bracket mounts the device sideways with or without us...

Page 18: ...the perfect choice when the power supply has no DC OK function Two light emitting diode LEDs and two relay contacts signal when one of the two input voltages is not in range due to a non functioning...

Page 19: ...discharged during such an event which causes a voltage dip on the output Figure 24 and Figure 25 show two typical voltage dips Output Circuit Breakers Standard miniature circuit breakers MCB s or UL 1...

Page 20: ...DC must be installed with protection against touching Avoid return voltage for example from a decelerating motor or battery that is applied to the output terminals Keep a left right installation clea...

Page 21: ...Redundancy Devices can be paralleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The si...

Page 22: ...ide of the DC DC converter with a distance of 1 cm 0 39 in The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure Figure 26 1 1 Redundant Co...

Page 23: ...28 Mounting Orientation A upright standard Figure 29 Mounting Orientation B upside down Figure 30 Mounting Orientation C table top Figure 31 Mounting Orientation D horizontal with input on the left Fi...

Page 24: ...24 Rockwell Automation Publication 1606 RM124A EN P September 2021 DC DC Converter 48V 48V 5 A 240 W Reference Manual Notes...

Page 25: ...closures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application I...

Page 26: ...edgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installat...

Reviews: