AC Input
The device is suitable to be supplied from TN, TT, or IT mains networks.
Attributes
Values
Notes
AC input
Nom
AC 100…240V
—
AC input range
Min
90…264V AC
Continuous operation
Min
264…300V AC
For 500 ms max
Allowed voltage L or N to earth
Max
300V AC
Continuous according to IEC 60664-1
Input frequency
Nom
50…60 Hz
±6%
Turn-on voltage
Typ
75V AC
Steady-state value, see
Shut-down voltage
Typ
54V AC
Steady-state value, see
External input protection
The device is designed, tested, and approved for branch circuits up to 20 A
without additional protection device. If an external fuse is used, do not use
circuit breakers smaller than 6A B- or 4A C-Characteristic. Smaller circuit
breakers may cause a nuisance tripping of the circuit breaker.
Attributes
Values
Notes
AC 100V
AC 120V
AC 230V
Input current
Typ
1.15 A
1.0 A
0.60 A
At 24V, 2.5 A, see
Power factor
Typ
0.58
0.55
0.47
At 24V, 2.5 A, see
Start-up delay
Typ
50 ms
50 ms
48 ms
See
Rise time
Typ
18 ms
18 ms
18 ms
At 24V, 2.5 A constant current load, 0 mF load capacitance, see
Typ
52 ms
52 ms
50 ms
At 24V, 2.5 A constant current load, 2 mF load capacitance, see
Turn-on overshoot
Max
100 mV
100 mV
100 mV
See
Figure 1 - Input Voltage Range
Figure 2 - Turn-on Behavior, Definitions
Turn-on
90V
Rated
input range
500 ms max
V
IN
P
OUT
300V AC
264V
Shut
-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Figure 3 - Input Current Versus Output Load at 24V Output Voltage
Figure 4 - Power Factor Versus Output Load at 24V Output Voltage
2.5 A
0
1.0
1.5
0
0.25
0.5
1.25 A
Input Current, Typ
2.0
Output Current
0.75
1.0
a) 100V AC
b) 120V AC
c) 230V AC
b
c
a
0.5
2.5 A
0.5
1.0
1.5
0.1
0.2
2.0
Output Current
0.3
0.4
0.5
0.6
Power Factor, Typ
a: 100V AC
b: 120V AC
c: 230V AC
b
c
a