ac/dc (120V) Isolated Input Module
14
Publication 1771-IN070B-EN-P - August 2002
EFT/B Immunity
IEC 61000-4-4
+1kV @ 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5
+1kV line-line (DM) and +2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
Keying
Between 22 and 24
Between 26 and 28
Field Wiring Arm
1771ĆWN
Wiring Arm Screw Torque
9 pound-inches (1.0Nm)
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I,
Division 2 Group A, B, C, D Hazardous Locations
CE
4
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 50082-2, Industrial Immunity
EN 61326, Meas./Control/Lab., Industrial Requirements
EN 61000-6-2, Industrial Immunity
European Union 73/23/EEC LVD Directive, compliant with:
EN 61131-2, Programmable Controllers
C-Tick
4
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
1
One or two 14-22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires. Use
copper wire only
2
14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller wire size may be required.
3
Refer to publication 1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines."
4
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details