Electrical installer
30
4
4.
OCDS008 digital chronothermostat (in association with
OTRG005 thermoregulator)
5.
Genius software for remote management of gas unit heaters
(in association with OTRG005 thermoregulator)
6.
External request
Control systems 3, 4 and 5 manage automatically the
power modulation of the unit on two power levels.
4.4.1
OCDS012 1-key basic control
How to connect the OCDS012 1-key basic control
The control must be installed on the wall in a suitable
position, using expansion screws.
1.
Access the connection terminal block according to Proce-
dure 4.2
2.
Use 3x1 mm
2
cable for connection.
3.
Connect the wires to the terminal block as shown in Figure
4.2
4.
For additional information refer to the instruction sheet sup-
plied with the OCDS012 optional.
The cable may not be longer than 20 metres.
Figure
4.2
1-key basic control connection
L1 Lockout lamp
P1 Reset button
5
6
7
L1
P1
OCDS012
3
1
9
3
1
9
L
1
4.4.2
OCTR000 2-key basic control
How to connect OCTR000 2-key basic control
The control must be installed on the wall in a suitable
position, using expansion screws.
1.
Access the connection terminal block according to Proce-
dure 4.2
2.
Use FRORR 6x1 mm
²
cable (available as OCVO015 optional,
with 5 m length).
3.
Connect the wires to the terminal block as shown in Figure
4.3
4.
For additional information refer to the instruction sheet sup-
plied with the OCTR000 optional.
The cable may not be longer than 20 metres.
Figure
4.3
2-key basic control connection
L1 Lockout lamp
P1 Reset button
Z1 Summer/winter switch
3
5
6
7
Z92
Z1
1
2
1
5
4
8
6
7
P1
7
8
6
4
1
5
L1
L
1
OCTR000
L
1
2
4.4.3
OTRG005 thermoregulator
How to connect OTRG005 thermoregulator
The thermoregulator must be installed on the wall in a
suitable position, using expansion screws.
Connection of the thermoregulator is made on the wir-
ing terminal block located in the electrical panel inside
the unit.
To connect OTRG005 thermoregulator:
1.
Access the connection terminal block according to Proce-
dure 4.2
2.
Remove 27 and 28 temporary jumpers on the terminal block
(Paragraph 1.4
15).
3.
Use FRORR 7x1 mm
²
cable (available as OCVO015 optional,
with 5 m length).
4.
Make electrical connections as described in Figure 4.4
and in Table 4.1
30.
5.
For additional information refer to the instruction sheet sup-
plied with the OTRG005 optional.
The cable may not be longer than 10 metres.
Table
4.1
OTRG005 thermoregulator connection
OTRG005 thermoregulator
Next-R
J1
1
Line
1
2
Neutral
N
J2
1
OF
5
2
RES
7
3
LF
6
4
FAN
C
5
REQ
Z91