Heating engineer
Installation, use and maintenance manual – Next-R
23
3
gas systems
fl
ue gas exhaust
fl
ue gas condensate discharge
Installation must also comply with the manufacturer's
provisions.
3.2
FUEL GAS SUPPLY
3.2.1
Gas connection
▶
3/4" M (R15, R20, R30, R40, R50 models)
▶
3/4" F (R60, R80 models)
on the rear, to the left (see dimensional diagrams, Paragraph
1.2
▶
Install an anti-vibration connection between the appliance
and the gas piping.
3.2.2
Mandatory shut-o
ff
valve
▶
Provide a gas shut-o
ff
valve (manual) on the gas supply line,
next to the appliance, to isolate it when required.
▶
Provide a three-piece pipe union.
▶
Perform connection in compliance with applicable regula-
tions.
3.2.3
Gas pipes sizing
The gas pipes must not cause excessive pressure drops and, con-
sequently, insu
ffi
cient gas pressure for the appliance.
3.2.4
Supply gas pressure
This appliance is equipped for a maximum gas supply
pressure of 50 mbar.
The appliance's gas supply pressure, both static and dynamic,
must comply with Table 3.1
23, with tolerance ± 15%.
Non compliant gas pressure (Table 3.1
23) may
damage the appliance and be hazardous.
Table
3.1
Gas network pressure
Gas supply pressure [mbar]
Product
category
Countries of destination
G20
G25
G25.1
G25.3
G2.350
G27
G30
G31
II
2H3B/P
AL, BG, CH, CY, CZ, DK, EE, FI, GR, HR, IT, LT, LV,
MK, NO, RO, SE, SI, SK, TR
20
30
30
AT, CH
20
50
50
II
2H3P
AL, BG, CH, CZ, ES, GB, GR, HR, IE, IT, LT, LV, MK,
PT, SI, SK, TR
20
37
RO
20
30
AT
20
50
II
2ELL3B/P
DE
20
20
50
50
II
2Esi3P
FR
20
25
37
II
2Er3P
20
25
37
II
2H3B/P
HU
25
30
30
II
2HS3B/P
25
25
30
30
II
2E3P
LU
20
50
II
2L3B/P
NL
25
30
30
II
2L3P
25
37
II
2EK3B/P
20
25
30
30
II
2EK3P
20
25
30
II
2E3B/P
PL
20
37
37
I
2E
20
II
2ELwLs3B/P
20
13
20
37
37
II
2ELwLs3P
20
13
20
37
I
2E(R)
BE
20
25
I
2E(S)
20
25
I
3P
37
I
3P
IS
30
I
2H
LV
20
I
3B/P
MT
30
30
I
3B
30
The appliance gas supply pressure, both static and dynamic, must comply with the values in the Table, with a tolerance of ± 15%.
3.2.5
Vertical pipes and condensate
▶
Vertical gas pipes must be
fi
tted with siphon and discharge
of the condensate that may form inside the pipe.
▶
If necessary, insulate the piping.
3.2.6
LPG pressure reducers
With LPG the following must be installed:
▶
A
fi
rst stage pressure reducer, close to the liquid gas tank.
▶
A second stage pressure reducer, close to the appliance.
3.3
COMBUSTION PRODUCTS EXHAUST
Compliance with standards
The appliance is approved for connection to a