Set Time of day and day of week 

(If using programming)

1.  Press the MENU button.
2. Press SET TIME.
3.   Day of the week will be flashing. Use 

 or 

 to select the current  

day of the week.

4. Press NEXT.
5.   The current hour will be flashing. Use 

 or 

 to select the current hour.   

Note the correct a.m. or p.m. indicator is selected. 

6. Press NEXT.
7.   The minutes will be flashing.  Use 

 or 

 to select the current minutes. 

8. Press DONE when completed.

Custom Programming

This thermostat can be configured to have 7 Day or 5+1+1 programming. If 7 Day  

is selected, all seven days will need to be programmed individually. If 5+1+1 

programming is selected, Monday–Friday will be programmed together and 

Saturday and Sunday will need to be programmed individually.  There are four  

time periods for each day (WAKE, LEAVE, RETURN, SLEEP).
Follow the steps below to customize your program schedule:
1.    Select HEAT or COOL. Note: Heat and cool need to be programmed separately.
2.    Press MENU (If menu does not appear first, press RUN SCHED).
3.    Press SET SCHED. Note: Monday–Friday (or Monday if in 7 Day mode) will be 

displayed and the WAKE icon is shown. 

4.    Time will be be flashing. Use 

 or 

 to make your time selection for the 

WAKE time period for Monday–Friday (or Monday if in 7 Day mode).

5.    Press NEXT STEP.
6.    The set-point temperature will be flashing. Use 

 or 

 to make your  

set-point selection for the WAKE time period for Monday–Friday (or Monday  

if in 7 Day mode).

7.    Press NEXT STEP.
8.    Repeat steps 4 through 7 for the LEAVE time period, for the RETURN time 

period, and for the SLEEP time period for Monday–Friday (or Monday if in  

7 Day mode).

9    Repeat steps 4 through 8 for the Saturday WAKE, LEAVE, RETURN, and SLEEP 

time periods, and then again for the Sunday WAKE, LEAVE, RETURN, and 

SLEEP time periods for the 5+1+1 program schedule, and for each day for the 

7-day program schedule.

 

Notes

Auto Changeover: In Auto mode, users can toggle between Auto Heat or 

Auto Cool by pressing System only when the current mode has reached its 

temperature set point. To switch out of Auto mode, hold down System.  

To return to Auto mode, toggle the System key to Auto.
Programmable Fan: The programmable fan feature will run the fan continuously 

during any time period it is programmed to be on. This is the best way to keep 

the air circulated and to eliminate hot and cold spots in your building.
Reminders: Once a Reminder has been turned on and set, the elapsed time can 

be checked by navigating the Tech Setup step. The time can be reset by pressing 

and holding the third button from the left for 3 seconds. Resetting an expired 

Reminder can be done by pressing and holding the 3rd button from the left for 

3 seconds.

Programming Notes

This thermostat is pre-programmed for energy saving operation.  

The default program is below:

Default Program

Day of the 

Week 

Events 

Time 

Set-Point 

Temperature 

(HEAT)

Set-Point 

Temperature 

(COOL) 

Weekday 

Wake 

6 AM 

70°F (21°C) 

75°F(24°C) 

Leave 

8 AM 

62° F (17°C)

83°F(28° C) 

Return 

6 PM 

70°F (21°C) 

75°F(24°C) 

Sleep 

10 PM 

62°F (17°C) 

78°F(26°C) 

Saturday 

Wake 

6 AM 

70°F (21°C) 

75°F(24°C) 

Leave 

8 AM 

62°F (17°C) 

83°F(28°C) 

Return 

6 PM 

70°F (21°C) 

75°F(24°C) 

Sleep 

10 PM

62°F (17°C) 

78°F(26°C) 

Sunday 

Wake

6 AM 

70°F (21°C) 

75°F(24°C) 

Leave

8 AM 

62°F (17°C) 

83°F(28°C) 

Return

6 PM 

70°F (21°C) 

75°F(24°C) 

Sleep

10 PM 

62°F (17°C) 

78°F(26°C)

Customer S1.800.304.6563

Technical S1.800.445.8299

[email protected]

www.robertshaw.com • 352-00301-001

6

Year

Limited 

Warranty

Use Phone 

to Scan for 

Warranty Info

Customer S1.800.304.6563

Technical S1.800.445.8299

[email protected]

www.robertshaw.com • 352-00301-001

6

Year

Limited 

Warranty

Use Phone 

to Scan for 

Warranty Info

352-00307-001 Rev. B

Programming Notes

Programming Notes

15

16

13

14

Thermostat Quick Reference

© 2021 Robertshaw Controls Company. 

Robertshaw

®

 is a trademark of Robertshaw Controls Company.

Keypad Lockout

The installer can activate a keypad lockout after exiting Tech Setup.

Default Program

Contractor Call Number

If contractor call number is selected ON, the selected phone number will show in 

the display if there has been a continuous call for heating or cooling for 24 hours or 

if the FAN button is held down for 3 seconds. To remove the phone number from 

the display, hold the fan button down for 3 seconds.

Differential Setting

The second stage will turn ON at 2x the differential setting and OFF at 1x the 

differential setting. For example, if the differential setting is 0.5° for heating 

and the thermostat is set at 70°F, the first stage will turn on at 69.5°F. The 

second stage will turn on at 69°F and turn off at 69.5°F. If the third stage is 

used, the third stage will turn on at 68.5°F and turn off at 69°F.