Set Time of day and day of week
(If using programming)
1. Press the MENU button.
2. Press SET TIME.
3. Day of the week will be flashing. Use
or
to select the current
day of the week.
4. Press NEXT.
5. The current hour will be flashing. Use
or
to select the current hour.
Note the correct a.m. or p.m. indicator is selected.
6. Press NEXT.
7. The minutes will be flashing. Use
or
to select the current minutes.
8. Press DONE when completed.
Custom Programming
This thermostat can be configured to have 7 Day or 5+1+1 programming. If 7 Day
is selected, all seven days will need to be programmed individually. If 5+1+1
programming is selected, Monday–Friday will be programmed together and
Saturday and Sunday will need to be programmed individually. There are four
time periods for each day (WAKE, LEAVE, RETURN, SLEEP).
Follow the steps below to customize your program schedule:
1. Select HEAT or COOL. Note: Heat and cool need to be programmed separately.
2. Press MENU (If menu does not appear first, press RUN SCHED).
3. Press SET SCHED. Note: Monday–Friday (or Monday if in 7 Day mode) will be
displayed and the WAKE icon is shown.
4. Time will be be flashing. Use
or
to make your time selection for the
WAKE time period for Monday–Friday (or Monday if in 7 Day mode).
5. Press NEXT STEP.
6. The set-point temperature will be flashing. Use
or
to make your
set-point selection for the WAKE time period for Monday–Friday (or Monday
if in 7 Day mode).
7. Press NEXT STEP.
8. Repeat steps 4 through 7 for the LEAVE time period, for the RETURN time
period, and for the SLEEP time period for Monday–Friday (or Monday if in
7 Day mode).
9 Repeat steps 4 through 8 for the Saturday WAKE, LEAVE, RETURN, and SLEEP
time periods, and then again for the Sunday WAKE, LEAVE, RETURN, and
SLEEP time periods for the 5+1+1 program schedule, and for each day for the
7-day program schedule.
Notes
Auto Changeover: In Auto mode, users can toggle between Auto Heat or
Auto Cool by pressing System only when the current mode has reached its
temperature set point. To switch out of Auto mode, hold down System.
To return to Auto mode, toggle the System key to Auto.
Programmable Fan: The programmable fan feature will run the fan continuously
during any time period it is programmed to be on. This is the best way to keep
the air circulated and to eliminate hot and cold spots in your building.
Reminders: Once a Reminder has been turned on and set, the elapsed time can
be checked by navigating the Tech Setup step. The time can be reset by pressing
and holding the third button from the left for 3 seconds. Resetting an expired
Reminder can be done by pressing and holding the 3rd button from the left for
3 seconds.
Programming Notes
This thermostat is pre-programmed for energy saving operation.
The default program is below:
Default Program
Day of the
Week
Events
Time
Set-Point
Temperature
(HEAT)
Set-Point
Temperature
(COOL)
Weekday
Wake
6 AM
70°F (21°C)
75°F(24°C)
Leave
8 AM
62° F (17°C)
83°F(28° C)
Return
6 PM
70°F (21°C)
75°F(24°C)
Sleep
10 PM
62°F (17°C)
78°F(26°C)
Saturday
Wake
6 AM
70°F (21°C)
75°F(24°C)
Leave
8 AM
62°F (17°C)
83°F(28°C)
Return
6 PM
70°F (21°C)
75°F(24°C)
Sleep
10 PM
62°F (17°C)
78°F(26°C)
Sunday
Wake
6 AM
70°F (21°C)
75°F(24°C)
Leave
8 AM
62°F (17°C)
83°F(28°C)
Return
6 PM
70°F (21°C)
75°F(24°C)
Sleep
10 PM
62°F (17°C)
78°F(26°C)
Customer S1.800.304.6563
Technical S1.800.445.8299
www.robertshaw.com • 352-00301-001
6
Year
Limited
Warranty
Use Phone
to Scan for
Warranty Info
Customer S1.800.304.6563
Technical S1.800.445.8299
www.robertshaw.com • 352-00301-001
6
Year
Limited
Warranty
Use Phone
to Scan for
Warranty Info
352-00307-001 Rev. B
Programming Notes
Programming Notes
15
16
13
14
Thermostat Quick Reference
© 2021 Robertshaw Controls Company.
Robertshaw
®
is a trademark of Robertshaw Controls Company.
Keypad Lockout
The installer can activate a keypad lockout after exiting Tech Setup.
Default Program
Contractor Call Number
If contractor call number is selected ON, the selected phone number will show in
the display if there has been a continuous call for heating or cooling for 24 hours or
if the FAN button is held down for 3 seconds. To remove the phone number from
the display, hold the fan button down for 3 seconds.
Differential Setting
The second stage will turn ON at 2x the differential setting and OFF at 1x the
differential setting. For example, if the differential setting is 0.5° for heating
and the thermostat is set at 70°F, the first stage will turn on at 69.5°F. The
second stage will turn on at 69°F and turn off at 69.5°F. If the third stage is
used, the third stage will turn on at 68.5°F and turn off at 69°F.