1. Press MENU.
2. Press and hold TECHNICIAN SETUP for 3 seconds.
3. Configure the installer options as desired using the table below.
4. Use
or
to change settings and NEW STEP or PREV STEP to move
from one step to another. Note: Only press DONE when you want to exit the
Installer Setup options.
Installer Setup Menu
Installer Setup Menu
Installer Setup Menu
Installer Setup Menu
11
12
9
10
Settings
Display Adjustment Options
Default
Heating
Differential
The heating differential is factory
preset at 0.4°. This means that
whenever the room temperature
cools by 0.4° from the temperature
setting, the heating system will
turn on. If the heating system
turns on too often, increase the
temperature differential.
The heating differential setting is
adjustable from 0.2°F to 2°F.
0.4
Heat Pump
The thermostat can be optionally
configured to operate a heat pump.
Use
or
to configure the
setting.
OFF
for conventional
systems and
ON
for heat pump
systems.
0FF
System
Switch
The system switch can be
configured for the particular
application. Heat-Off-Cool, Heat-Off,
Cool-Off, Heat-Off- Cool-Auto.
Note: Emergency Heat is available
in heat pump mode only.
Use
or
until the
desired application is flashing.
AUTO
= (Auto Changeover)
0FF
Stages of
Heat and
Cool
If the heat pump is still
ON
, this
thermostat can be configured to
operate up to 2H/2C conventional,
or up to 4H/2C heat pump system.
Use
or
to select stages
of heat, press NEXT, then select
stages of cool. 3 or 4 heat will
use Y1 and Y2 as 1st and 2nd
stage of heat.
2
STAGES
Cooling Fan
Delay
The cooling fan delay setting delays
the fan from coming on in cool
mode and keeps it running after
the compressor shuts off for a short
time in order to save energy.
The cooling fan delay can be set
to
OFF,
15, 30, 60 or 90 seconds.
If 15, 30, 60 or 90 is selected, the
fan will not turn on for at least
the selected time when there
is a call for cool and will run for
at least the selected time after
satisfying the call for cool.
0FF
Settings
Display Adjustment Options
Default
Filter Change
Reminder
This setting will flash
FILT
in the
display after the elapsed run time
to remind the user to change the
filter. The
OFF
setting will disable
this feature.
The filter change reminder can
be adjusted from
OFF
to 2000
hours in 50 hour increments.
OFF
Room
Temperature
Calibration
This setting allows the installer to
change the calibration of the room
temperature display so that, for
example, the thermostat would read
72°F instead of 70°F.
The room temperature display
can be adjusted to read 3° above
or below the factory calibrated
temperature.
0
Minimum
Compressor
On-Time
The installer can select the minimum
run time for the compressor to help
protect the compressor from short-
cycling.
The minimum compressor run
time can be adjusted from
OFF
to 3, 4, or 5 minutes. If 3, 4, or 5
is selected, the compressor will
run for at least the selected time
before turning off (although the
fan may continue to run for a
short time).
OFF
Compressor
Short Cycle
Delay
The compressor short cycle delay
setting will not allow the compressor
to be turned on for 5 minutes after it
was last turned off in order to protect
the compressor.
The compressor short cycle
delay setting can be removed
by selecting
OFF
.
ON
Cooling
Differential
The cooling differential is factory
preset at 0.5°. This means that
whenever the room temperature
heats by 0.5° full degree from the
temperature setting, the cooling
system will turn on. If the cooling
system turns on too often, increase
the temperature differential.
The cooling differential setting is
adjustable from 0.2°F to 2°F.
0.5
Settings
Display Adjustment Options
Default
Heating
Temperature
Set-Point
Limit
This setting establishes a
maximum value above which
the set-point temperature value
cannot be raised.
Use
or
to
select the maximum heat
temperature set-point.
Range 44°F - 90°F
90°
Cooling
Temperature
Set-Point
Limit
This setting establishes a
maximum value above which
the set-point temperature value
cannot be lowered.
Use
or
to
select the minimum cool
temperature set-point.
Range 44°F - 90°F
44°
F° or C°
Select F for Fahrenheit temperature
display or select C for Celsius
display.
°F for Fahrenheit
°C for Celsius
F°
12 or 24
Hour Clock
Select a 12 or 24 hour clock setting.
Use
or
to select
12 or 24 hour clock.
12 Hour
Clock
Fan
Operation
Select
GAS
or
ELEC
depending
on the type of furnace.
GAS
or
ELEC
GAS
Morning
Recovery
This setting will start heating early
to bring the building temperature
to its programmed set-point by
the beginning of the
WAKE
time
period.
Use
or
to turn on or off.
ON
F OR C SET
Program
Options
This thermostat can be configured to
have 7 Day, 5+1+1 programming or
be non-programmable.
If 7 Day is selected, in Set Time
all seven days will need to be
programmed individually.
If 5+1+1 programming is selected,
in Set Time Monday–Friday will
be programmed together and
Saturday and Sunday will need to be
programmed individually.
If 0d is selected, the thermostat
becomes non-programmable.
Use
or
to select
7d
for
7 day,
5d
for 5+1+1, or
Od
for
non-programmable.
5d
Display
Light
The display light can be configured to
come on when any key is pressed or to
stay on all of the time.
AUTO
- Any key ON
ON
- Always ON
AUTO
Contractor
Call
Number
The thermostat allows installers to put
their phone number in the display.
If selected
ON
, the input screen
will appear after pressing Next
Step. Use
or
to select
the desired telephone number
and the
FAN
or
SYSTEM
key to
change characters.
OFF
Beep
The thermostat can be configured to
make an audible beep when any key
is pressed.
If
ON
is selected,
the beep will sound.
If
OFF
is selected,
the beep will be silenced.
ON