SECTION 13: T
ROUBLESHOOTING
55
C
ont
act
R
o
ber
ts-Gor
don LLC
at www
.r
g-inc.com.
Chec
k f
or obstr
uctions in
or
if
ices and air plat
es
inside the b
u
rner
.
Chec
k the ther
most
at and
chec
k the contin
uit
y of
the g
round w
ir
e
.
Does the b
u
rner tur
n of
f
when the call f
or heat
ends?
No
Ye
s
R
eplace/corr
ect w
ir
e
s
.
R
eplace ignition module
.
Ar
e the w
ir
e
s
connecting the module
and electr
odes OK?
Ye
s
No
Does the b
u
rner
st
a
y
on?
No
Ye
s
T
u
rn
v
a
lv
e ON.
R
eplace ignition module
.
R
eplace/corr
ect w
ir
e
s
.
R
eplace g
as v
a
lv
e
.
Is the knob on the g
as v
a
lv
e
in the ON position?
Ye
s
No
Ar
e the w
ir
es connecting
the ignition module OK?
Ye
s
Chec
k g
as line st
op coc
k.
C
ont
act g
as compan
y.
Is ther
e g
as outlet
pr
essur
e a
v
ailab
le dur
ing
the ignition per
iod?
No
Measur
e v
olt
age on v
a
lv
e
te
rminals
. Is ther
e 24
V
dur
ing ignition time?
Ye
s
No
Is the inlet g
as pr
essur
e
dur
ing ignition corr
ect?
(Natur
al 5.0" min.,
LP should be 1
2.0")
Ye
s
No
A
djust the
v
a
lv
e pr
essur
e
.
Is the g
as outlet pr
essur
e
3.5" f
or Natur
al Gas
(1
0.5" f
or LP)?
Ye
s
P
u
rge Lines
.
W
e
re
the g
as lines
pur
ged of air?
No
Ye
s
Does the
b
u
rner light?
No
Ye
s
Ye
s
Ye
s
No
No
®
TR
OUBLESHOO
T ENDS.
If pr
ob
lems per
sist, cont
act
R
OBER
TS GORDON
Independent Distr
ib
ut
or
.
Ye
s