ROBERTS GOR DON
®
T F-S
E RIE S
S
UB MI TT AL
S
HEE T
© 2004 Roberts-Gordon
APPL ICATION S, ENGI NEE RING AND DET AI LE D GUID ANCE ON SYST EMS DE SIGN, INSTAL LATI ON AND PRODUCT PE RFORMANCE IS AVAI LABLE UPON RE QUEST. ROBERT S GORDON
®
PRODUCT S ARE T O BE
INSTAL LE D ONL Y IN ACCORDANCE WI TH L OCAL L AWS, CODES AND REGUL AT IONS, AND ONLY BY A CONT RACT OR QUALI FIE D I N THE I NST ALL AT ION AND SE RVICE OF GAS-FIRE D HE AT ING EQUI PME NT.
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
Standard Reflector
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
6
35
63
35
16
89
161
89
TF-160
6
38
66
38
16
97
168
97
TF-200
6
40
71
40
16
102
181
102
TF-250
6
46
77
46
16
117
196
117
TF-300
6
50
80
50
16
127
204
127
TF-350
8
52
82
52
21
133
209
133
TF-380
8
52
82
52
21
133
209
133
A
C
D
B
One Side Reflector
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
6
9
63
47
16
23
161
120
TF-160
6
9
70
54
16
23
178
138
TF-200
6
9
77
59
16
23
196
150
TF-250
6
9
83
65
16
23
211
166
TF-300
6
9
86
69
16
23
219
176
TF-350
8
9
88
73
21
23
224
186
TF-380
8
9
88
73
21
23
224
186
A
C
D
B
Two Side Reflectors
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
TF-120
6
23
66
23
16
59
168
59
TF-160
6
25
72
25
16
64
183
64
TF-200
6
27
78
27
16
69
199
69
TF-250
6
32
84
32
16
82
214
82
TF-300
6
35
88
35
16
89
224
89
TF-350
8
40
91
40
21
102
232
102
TF-380
8
40
91
40
21
102
232
102
A
C
D
B