VA N TA G E
®
H E
I N S TA L L AT I O N M A N U A L
R O B E R T S
-
G O R D O N
pg 42
Recommended Minimum Mounting Height*
Model
Rate
Length "A"
Space
Spot Indoor
Spot Outdoor
Feet
Meters
Feet
Meters
Feet
Meters
Feet
Meters
HE- 40
40,000 Btu/hr
10
3
8 to 10
2.4 to 3.0
8
2.4
8
2.4
HE- 60
60,000 Btu/hr
20
6
10 to 12
3.0 to 3.7
9
2.7
9
2.7
HE- 80
80,000 Btu/hr
20
6
12 to 15
3.7 to 4.6
11
3.4
10
3.0
HE-100
100,000 Btu/hr
30
9
12 to 15
3.7 to 4.6
12
3.7
12
3.7
HE-125
125,000 Btu/hr
40
12
15 to 20
4.6 to 6.0
15
4.6
12
3.7
HE-150
150,000 Btu/hr
50
15
20 to 25
6.0 to 7.6
20
6
15
4.6
HE-175
175,000 Btu/hr
60
18
25
7.6
23
7
15
4.6
Gas Pressure at Manifold:
Natural Gas:
3.5" W.C.
LP Gas:
10.5" W.C.
Pipe Connection:
3/4" NPT
Dimensions:
Vent Connection Size: 4" (10 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.
Electrical Rating: (All Models)
120V, 60 Hz., 1.0 Amp (run) 5.0 Amp (start)
Gas Inlet Pressure:
Natural Gas: 4.6" W.C. Minimum (for HE 40,60,80,100,
125,150) 14.0" Maximum
5.0" W.C. Minimum (for HE-175)
14.0" Maximum
LP Gas:
11.0" W.C. Minimum
14.0" Maximum
Section 15. General Specifications
General Specifications for VANTAGE
®
HE heaters are as follows:
*Clearances to combustibles must
be maintained in all cases.
Burner Rear View
13.75"
(35 cm)
9.5" (24 cm)
Reflector
Burner Side View
Turbulator
(Some Models)
Length "A"
17.5" (44 cm)