SECTION 9: V
ENTING
21 of 29
FIGURE 17: Condensate Check Valve
FIGURE 18: Condensate Tee - Discharge Side
9.6 Condensate Trap and Condensate Tee
Install condensate trap assembly (optional) (P/N
01327001), on inlet side of EP-100 Series p
u
mp
assembly,
See Page 21, Figure 17
.
It is possible to eliminate the condensate trap assem-
bly on the p
u
mp if the one-inch threaded hole is
pl
u
gged. This arrangement
w
ill permit drainage of
condensate thro
u
gh the p
u
mp and o
u
tside
v
ia
horizontal (pitched) discharge line.
The condensate trap assembly in the discharge line
can be eliminated if the discharge line is horizontal
thro
u
gh the
w
all and pitched do
w
n at least one inch
per foot. A condensate trap on the discharge side is
req
u
ired if there is a
v
ertical rise in the discharge line.
Description
Part Number
Condensate Val
v
e Assembly
01327001
Tee 4" (10 cm)
01330203
Drain Cap 4" (10 cm)
02718851