SECTION
4:
PROGRAMMING OPTIONS
9
4.11
CHANGING THE OVERRIDE LIMITS
4.11.1 Press PROG and enter the code 1805.
Press ENTER.
Enter 1 for DATA.
4.11.2 These are the settings for limit of the override for
both time and temperature.
The screen will now show:
Press ENTER to skip the calibration screens.
There will be one displayed for each zone. The
calibration of the sensors will be conducted by
installer.
4.11.3 The screen will now show:
The default maximum override of 8 hours is dis-
played. To alter the number, enter the new number
and press ENTER.
4.11.4 The screen will now show:
The default upper offset limit of 2
O
C is displayed.
To alter the number, enter the new number and
press ENTER.
4.11.5 The screen will now show:
The default upper offset limit of 18
O
F or 5
O
C is dis-
played. To alter the number, enter the new number
and press ENTER.
4.11.6 If any mistakes were made during the program-
ming sequence, see
Page 5, Section 4.1 for cor-
rective action.
4.11.7 At the prompt for a zone to alter, press RUN to
return to the menu.
4.11.8 Press RUN again to return to Normal (Run) Mode
from the menu.
ENTER LOWER TEMP
OFFSET LIMIT
: 05
ENTER UPPER TEMP
OFFSET LIMIT
: 02
ENTER MAXIMUM
OVERRIDE
:08
CALIBRATION NO.1
SETTING
:00