61
As a policy of continual improvement, RMF reserves the right to alter the specification without prior notice.
201.028 REV 1
Date of Issue: 18 June 2018
11.1.1.3 Register Functions
11.1.1.3.1 Test Mode
Factory set value: 0
This is the "test mode", each bit represents an option corresponding to a tick box on the CMS settings screen (see
our RMF-View software and in the CMS manual).
Each bit of the register encodes one tick box.
The factory set mode is 0 for all bits, so all the tick boxes are turned off. You may want to turn on bit 8 (disable
low flow alarm when clean) if you have a very clean system.
Here are the bit definitions:
Bit
Function
Comment
0
CYCLE_COTINUOUS
Continuous Testing
1
START_TEST_AUTOMATICALLY
Start Testing Automatically
2
CONTINUOUS_STOP_WHEN_CLEAN
Stop Testing When Clean
3
CONTINUOUS_LOG_EVERY_TEST
Continuous Mode: Log Every Test
4
CONTINUOUS_CONFIRM_TARGET
Repeat final test to confirm target level achieved
5
RESERVED
6
RESERVED
7
SIMULATE
Produces simulated test results
8
LOW_FLOW_CLEAN_DISABLED
Prevents spurious low flow alarms on clean systems
Table 11B Test Mode Register Bit Definitions
There is some general information about what these options do in section 6.3.3.
11.1.1.3.2 Command Register
This is register 21. It is special in that writing a number to this register does not store the number, but instead
commands the CMS
to perform a function according to the number written. The main command is ``START’’, but
the others are documented here for completeness and avoidance.
Bit
Function
Comment
1
START TEST
Start or Restart a test
2
RECALCULATE
3
FORCE OUTPUT 1 ON
4
FORCE OUTPUT 1 OFF
5
FORCE OUTPUT 2 ON
6
FORCE OUTPUT 2 OFF
7
TEST MODE ON
Flashes LED and exercises outputs
8
TEST MODE OFF
9
STOP
Abort a test in progress
10
LOG ERASE
Caution!
11
LOG SEEK END
12
LOG SEEK PREVIOUS
Table 11C Command Register
Summary of Contents for CMS 2