- 29 -
SD-1GH
6
Operations and Functions
6-1. Gas Alarm Activation
Gas alarm: Triggered when the concentration of detected gas reaches or exceeds the alarm setpoint value.
NOTE
The alarm setpoint is factory-set. The alarm delay time (standard: 2 seconds) can be cancelled if not
needed.
<Display Operation>
Gas Concentration Display
If the gas concentration rises above the detection range (Over Scale),
"∩∩∩∩
" is displayed.
Power Indicator Lamp (POWER: Green)
During operation, this lights up continuously.
Alarm Indicator Lamp (ALM: Red)
It lights up when the alarm setpoint value is reached or exceeded.
<Contact Activation>
The contact is activated when the gas concentration reaches or exceeds the alarm setpoint value (only
when the alarm is used).
The contact activation automatically resets when the gas concentration drops below the alarm setpoint
value.
Alarm delay time (2 seconds)
Alarm lamp (ALM)
Alarm contact (terminal plate 4, 5)
Alarm setpoint
C
onc
ent
rat
ion
0
Time