background image

 

 

 

61-1000RK-05 Combustible Gas Detector• 5

 

Description

 

This section describes the components of the combustible gas detector. The detector 
includes the sensing elements, flame arrestor, flame arrestor guard, detector housing, and 
detector leads. 

 

Sensing elements

 

Two sensing elements are protected within the detector assembly. Through a series of 
thermal and electronic reactions, these elements produce an electrical output that is 
proportional to the detection range of the detector.

 

Flame arrestor

 

The porous flame arrestor allows the target gas to diffuse into the detector assembly and 
contact the sensing elements. The flame arrestor also contains sparks within the detector.

 

Flame arrestor guard

 

The flame arrestor guard is permanently bonded to the detector housing and protects the 
flame arrestor from impact damage.

 

Detector housing

 

The sensing elements and flame arrestor are installed within the detector housing. 
Mounting threads (1/2 in. NPT) at the top of the detector allow you to mount the 
combustible gas detector into the bottom conduit hub of the junction box. A rainshield 
screws onto the bottom of the detector. The rainshield helps protect the detector from 
debris in the monitoring environment.

 

Detector leads

 

Four color-coded leads extend from the top of the detector. The leads allow you to connect 
the combustible gas detector to the amplifier.

 

Junction Box

 

The junction box allows you to install the detector at a mounting site that is remote from a 
controller, and it protects the detector wiring connections. Two conduit hubs allow you to 
mount the detector to the junction box and connect the wiring from the detector to a 
controller. Three spacers installed on the back of the junction box control the distance of 
the junction box from a mounting surface and insure that there is enough room to install a 
calibration cup on the detector during calibration.

The bottom conduit hub includes a 3/4 in. x 1/2 in. reducer that allows you to screw the 
detector into the hub. The terminal block within the junction box facilitates the wiring 
process. A cover on the front of the junction box allows access to the interior of the 
junction box.

Summary of Contents for 61-1000RK-05

Page 1: ...www rkiinstruments com 61 1000RK 05 Combustible Gas Detector Operator s Manual Part Number 71 0087RK Revision A Released 12 14 05...

Page 2: ...placement costs local repair costs transportation costs or contingent expenses incurred without our prior approval THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATION...

Page 3: ...unting the Combustible Gas Detector 6 Wiring the Combustible Gas Detector 7 Startup Introducing Incoming Power 9 Setting the Zero Signal 9 Maintenance 10 Preventive Maintenance 10 Troubleshooting 11 R...

Page 4: ...ble gas detector Specifications WARNING Do not use this product in a manner not specified in this instruction manual Table 1 lists specifications for the combustible gas detector NOTE The following sy...

Page 5: ...low you to mount the combustible gas detector into the bottom conduit hub of the junction box A rainshield screws onto the bottom of the detector The rainshield helps protect the detector from debris...

Page 6: ...ing when you select the mounting site Select a site where the detector is not likely to be bumped or disturbed Make sure there is sufficient room to perform start up maintenance and calibration proced...

Page 7: ...hielded cable or four wires in conduit through the top conduit hub of the junction box WARNING To maintain the explosion proof classification of the LEL detector junction box combination a conduit sea...

Page 8: ...stible Gas Detector 8 Figure 2 Wiring the Combustible Gas Detector to a Controller Combustibles Detector DetectorWires Controller LEL Detector Terminals Green Red Green Red Terminal Strip Black White...

Page 9: ...tion manual CAUTION Allow the detector to warm up for 5 minutes before you continue with the next section Setting the Zero Reading Setting the Zero Reading CAUTION If you suspect the presence of combu...

Page 10: ...xternal alarms before performing this test 1 Place the controller into its calibration program or disable external alarms 2 Verify that the controller display reading is 0 LEL If the controller readin...

Page 11: ...p 4 Table 2 Troubleshooting the Combustible Gas Detector Condition Symptom s Probable Causes Recommended Action Fail Condition Controller indicates a fail condition The detector wiring is disconnected...

Page 12: ...arms NOTE Calibrating the combustible detector may cause alarms Be sure to put the controller into its calibration program or disable external alarms before continuing Setting the Zero Reading CAUTION...

Page 13: ...of the calibration kit in a safe and convenient place Parts List Table 3 lists replacement parts and accessories for the 61 1000RK 05 combustible gas detector Table 3 Parts List Part Number Descriptio...

Reviews: