7. SPECIFICATIONS 

 

Inputs 

Number of inputs: 

2 points   

Isolated between each channel: 

Thermocouple input, Voltage (low) input 

Not isolated between each channel: 

RTD input, Voltage (high) input,   
Current input 

Input type: 

 

Thermocouple 

K, J, T, S, R, E, B, N (JIS-C1602-1995) 

  

PLII 

(NBS) 

  

W5Re/W26Re 

(ASTM-E988-96) 

 

RTD Pt100 

(JIS-C1604-1997) 

   

JPt100 (JIS-C1604-1989, Pt100 of   

  

 

JIS-C1604-1981) 

 

Voltage (low) 

0 to 100 mV 

 

Voltage (high) 

0 to 5 V, 0 to 10 V, 1 to 5 V 

 

Current 

0 to 20 mA, 4 to 20 mA 

Sampling cycle: 

500 ms 

PV bias: 

Input span to 

+

Input span 

CT input: 

2 points 

 

0.0 to 30.0 A (CTL-6P-N) or 

 

0.0 to 100.0 A (CTL-12-S56-10L-N) 

 

 

Outputs 

Number of outputs: 

2 points   
(Isolated between input and output, and 

between output and power supply) 

Output type: 

 Relay contact: 

250 V AC, 3 A (Resistive load)   

  

1a 

contact 

   

Electrical life 300,000 times or more   

  

(Rated 

load) 

 Voltage pulse: 

0/12 V DC   

   

(Load resistance 600 

 or more) 

 Current: 

0 to 20 mA DC, 4 to 20 mA DC 

   

(Load resistance 600 

 or less) 

 Voltage: 

0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC 

   

(Load resistance 1 k

 or more) 

 

 

Control action 

Number of controls: 

2 points 

Control method: 

Brilliant PID control 

Reverse action or direct action is 

selectable (Specify when ordering) 
Heat/cool control is selectable   

(Specify when ordering) 

Additional function: 

Autotuning function 

 

 

Events 

Number of events: 

2 points/channel 

Event type: 

Temperature event: 
 

Deviation high, Deviation low, 

 

Deviation high/low, Band,   

 

Process high, Process low 

Heater break alarm,   

Control loop break alarm,   

Burnout, Temperature rise completion 

 

 

Option 

 

Event input (DI) 

Number of inputs: 

1 point 

Input type: 

Dry contact input 

Input voltage: 

24 V DC (Rated) 

Input current: 

Approx. 6 mA 

Input details: 

Control RUN/STOP,   

Event interlock release   
(Specify when ordering) 

 

Event output (DO) 

Number of outputs: 

2 points 

Output type: 

Relay contact output 

250 V AC, 1 A (Resistive load) 
1a contact 

Electrical life 300,000 times or more   

(Rated load) 

Output details: 

Temperature event, Heater break alarm, 
Control loop break alarm, Burnout, 

Temperature rise completion 

(Specify when ordering) 

 

 

Ethernet communication 

Physical layer: 

Ethernet 
10BASE-T/100BASE-TX automatic 
recognition 

Application layer: 

Modbus/TCP 

Communication data: 

Based on Modbus message format 

Connector type: 

RJ-45 

Maximum connections: 

Up to 30 temperature control modules 
can be connected to one 
V-TIO-P/V-TIO-Q module. 

 

 

Others 

Power supply voltage: 

24 V DC 

Power supply voltage range: 

21.6 V DC to 26.4 V DC 

Current consumption: 

With event input/output (option): 
 

220 mA max./module 

Without event input/output (option): 
 

200 mA max./module 

Rush current: 

12 A/module max. 

Allowable ambient temperature: 

10 to 

+

50 

°

Allowable ambient humidity: 

5 to 95 %RH 
Absolute humidity:   
MAX.W.C 29 g/m

3

 dry air at 101.3 kPa 

Weight: 

With event input/output (option): 
 

Approx. 270 g 

Without event input/output (option): 
 

Approx. 260 g 

 

 

Standard 

Safety standard: 

UL: 

UL61010A-1 

CSA: CAN/CSA-C22.2 No1010.1 

CE marking: 

LVD:  EN61010-1 
EMC: EN55011, EN61326-1 

C-Tick: 

AS/NZS CISPR 11   
(equivalent to EN55011) 

 

Summary of Contents for V-TIO-P

Page 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Page 2: ...dule for Ethernet heat control Q Module for Ethernet heat cool control 2 Control action Each channel common code For heat control F PID action with autotuning AT reverse action D PID action with autotuning AT direct action For heat cool control B Heat cool PID action with autotuning AT air cooling W Heat cool PID action with autotuning AT water cooling 3 Input range Each channel common code Thermo...

Page 3: ...office or the agent 3 PARTS DESCRIPTION Terminal cover Indication lamps 1 Address setting switch Terminal cover Indication lamps 2 Event connector Ethernet communication side Temperature control side FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 5 4 3 2 1 0 9 8 7 6 5 5 4 3 2 1 0 9 8 7 6 5 Modular connector for Ethernet RJ 45 Indication lamp 3 Indication lamp 4 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVEN...

Page 4: ...e this one The communication speed sets the same value as a temperature control side DIP switch 3 setting Temperature control side setting Set the communication speed and data bit configuration for internal communication by using the DIP switch 3 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON DIP switch 3 Right side ON OFF Terminal base Module mainframe 1 2 Communication speed OFF OFF Don t set this one ON...

Page 5: ...with the event connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected 110 Usage example of SRVP 01 Unit mm Approx 50 Connector plug SRVP 01 sold separately 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom of the module ...

Page 6: ... RTD input use low resistance lead wire with no difference in resistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply...

Page 7: ...ptional This is a connector installed in the V TIO P V TIO Q module only when provided with the event input DI or the event output DO 1 6 Event connector socket Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in Connector plug Wiring Use the following connector plug as that connected to the event input output connector Connector plug is sold separately SRVP 01 Front screw ...

Page 8: ...action is selectable Specify when ordering Heat cool control is selectable Specify when ordering Additional function Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input DI Number of inp...

Reviews: