7. SPECIFICATIONS
Inputs
Number of inputs:
2 points
Isolated between each channel:
Thermocouple input, Voltage (low) input
Not isolated between each channel:
RTD input, Voltage (high) input,
Current input
Input type:
•
Thermocouple
K, J, T, S, R, E, B, N (JIS-C1602-1995)
PLII
(NBS)
W5Re/W26Re
(ASTM-E988-96)
•
RTD Pt100
(JIS-C1604-1997)
JPt100 (JIS-C1604-1989, Pt100 of
JIS-C1604-1981)
•
Voltage (low)
0 to 100 mV
•
Voltage (high)
0 to 5 V, 0 to 10 V, 1 to 5 V
•
Current
0 to 20 mA, 4 to 20 mA
Sampling cycle:
500 ms
PV bias:
−
Input span to
+
Input span
CT input:
2 points
0.0 to 30.0 A (CTL-6P-N) or
0.0 to 100.0 A (CTL-12-S56-10L-N)
Outputs
Number of outputs:
2 points
(Isolated between input and output, and
between output and power supply)
Output type:
•
Relay contact:
250 V AC, 3 A (Resistive load)
1a
contact
Electrical life 300,000 times or more
(Rated
load)
•
Voltage pulse:
0/12 V DC
(Load resistance 600
Ω
or more)
•
Current:
0 to 20 mA DC, 4 to 20 mA DC
(Load resistance 600
Ω
or less)
•
Voltage:
0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC
(Load resistance 1 k
Ω
or more)
Control action
Number of controls:
2 points
Control method:
Brilliant PID control
Reverse action or direct action is
selectable (Specify when ordering)
Heat/cool control is selectable
(Specify when ordering)
Additional function:
Autotuning function
Events
Number of events:
2 points/channel
Event type:
Temperature event:
Deviation high, Deviation low,
Deviation high/low, Band,
Process high, Process low
Heater break alarm,
Control loop break alarm,
Burnout, Temperature rise completion
Option
Event input (DI)
Number of inputs:
1 point
Input type:
Dry contact input
Input voltage:
24 V DC (Rated)
Input current:
Approx. 6 mA
Input details:
Control RUN/STOP,
Event interlock release
(Specify when ordering)
Event output (DO)
Number of outputs:
2 points
Output type:
Relay contact output
250 V AC, 1 A (Resistive load)
1a contact
Electrical life 300,000 times or more
(Rated load)
Output details:
Temperature event, Heater break alarm,
Control loop break alarm, Burnout,
Temperature rise completion
(Specify when ordering)
Ethernet communication
Physical layer:
Ethernet
10BASE-T/100BASE-TX automatic
recognition
Application layer:
Modbus/TCP
Communication data:
Based on Modbus message format
Connector type:
RJ-45
Maximum connections:
Up to 30 temperature control modules
can be connected to one
V-TIO-P/V-TIO-Q module.
Others
Power supply voltage:
24 V DC
Power supply voltage range:
21.6 V DC to 26.4 V DC
Current consumption:
With event input/output (option):
220 mA max./module
Without event input/output (option):
200 mA max./module
Rush current:
12 A/module max.
Allowable ambient temperature:
−
10 to
+
50
°
C
Allowable ambient humidity:
5 to 95 %RH
Absolute humidity:
MAX.W.C 29 g/m
3
dry air at 101.3 kPa
Weight:
With event input/output (option):
Approx. 270 g
Without event input/output (option):
Approx. 260 g
Standard
Safety standard:
UL:
UL61010A-1
CSA: CAN/CSA-C22.2 No1010.1
CE marking:
LVD: EN61010-1
EMC: EN55011, EN61326-1
C-Tick:
AS/NZS CISPR 11
(equivalent to EN55011)