RKC INSTRUMENT V-TIO-P Instruction Manual Download Page 5

 

IMS01P08-E3

 

5

5. MOUNTING 

 
 
 
 
 
 

 

5.1 Mounting Cautions 

(1) This instrument is intended to be used under the following 

environmental conditions. (IEC61010-1)

   

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]

 

(2)  Use this instrument within the following ambient temperature 

and ambient humidity. 

• 

Allowable ambient temperature: 

10 to 

+

50 

°

• 

Allowable ambient humidity: 

5 to 95 % RH 

(Absolute humidity: MAX.W.C 29 g/m

3

 dry air at 101.3 kPa) 

(3)  Avoid the following when selecting the mounting location.

 

• 

Rapid changes in ambient temperature, which may cause 
condensation. 

• 

Corrosive or inflammable gases. 

• 

Direct vibration or shock to the mainframe. 

• 

Water, oil, chemicals, vapor or steam splashes. 

• 

Excessive dust, salt or iron particles. 

• 

Excessive induction noise, static electricity, magnetic fields or 
noise. 

• 

Direct air flow from an air conditioner. 

• 

Exposure to direct sunlight. 

• 

Excessive heat accumulation. 

(4) Mounting consideration  

• 

Install the module 200 mm away from the main power line. 

• 

Ensure at least 50 mm space on top and bottom of the control 
unit for maintenance and environmental reasons. 

 

5.2 Dimensions 

 

110

 

6.8

 

40.5

125

 

78

 

5

(Unit: mm)

 

 

The above figure shows when provided with the event 
connector, but the same also when not provided with the 
connector. 

 

 

Depth in connector mounting

 

Conduct installation in consideration of the sizes of the 
connector and cable when connector-connected. 

 

110

 

[Usage example of SRVP-01]

 

(Unit: mm)

Approx. 50

 

Connector (plug): 
SRVP-01 (sold separately)

 

5.3 DIN rail Mounting 

 

Mounting procedures 

1. 

Pull down the mounting bracket at the bottom of the module 
(A). Attach the hooks on the top of the module to the DIN rail 
and push the lower section into place on the DIN rail (B).   

 

(B) Push

Mounting 

bracket

DIN rail

(A) Pull down 

 

 

2. 

Slide the mounting bracket up to secure the module to the 
DIN rail. 

 

Locked 

 

 

 

End Plate mounting 

Hold tight both ends of the modules jointed together with the end 
plates and then fix the end plates with screws. Even if only one 
V-TIO-P/V-TIO-Q module is used, also hold tight both ends of 
the module with the end plates. 

 

End Plate

V-TIO-P/V-TIO-Q

 

 module 

End Plate

Joint connector cover 

*

 

 

For the conservation of the contact of connector, install a joint 
connector cover in module of both ends.

 

 

 

Removing procedures 

Pull down a mounting bracket with a blade screwdriver (A). Lift 
the module from bottom, and take it off (B). 

 

(A) Pull down 

(B) Lift and take off 

 

 

 

 

 
To prevent electric shock or instrument failure, 
always turn off the power before mounting or 
removing the instrument. 

!

 

WARNING 

Summary of Contents for V-TIO-P

Page 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Page 2: ...dule for Ethernet heat control Q Module for Ethernet heat cool control 2 Control action Each channel common code For heat control F PID action with autotuning AT reverse action D PID action with autotuning AT direct action For heat cool control B Heat cool PID action with autotuning AT air cooling W Heat cool PID action with autotuning AT water cooling 3 Input range Each channel common code Thermo...

Page 3: ...office or the agent 3 PARTS DESCRIPTION Terminal cover Indication lamps 1 Address setting switch Terminal cover Indication lamps 2 Event connector Ethernet communication side Temperature control side FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVENT4 5 4 3 2 1 0 9 8 7 6 5 5 4 3 2 1 0 9 8 7 6 5 Modular connector for Ethernet RJ 45 Indication lamp 3 Indication lamp 4 FAIL RUN RX TX EVENT1 EVENT2 EVENT3 EVEN...

Page 4: ...e this one The communication speed sets the same value as a temperature control side DIP switch 3 setting Temperature control side setting Set the communication speed and data bit configuration for internal communication by using the DIP switch 3 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 ON DIP switch 3 Right side ON OFF Terminal base Module mainframe 1 2 Communication speed OFF OFF Don t set this one ON...

Page 5: ...with the event connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected 110 Usage example of SRVP 01 Unit mm Approx 50 Connector plug SRVP 01 sold separately 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom of the module ...

Page 6: ... RTD input use low resistance lead wire with no difference in resistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply...

Page 7: ...ptional This is a connector installed in the V TIO P V TIO Q module only when provided with the event input DI or the event output DO 1 6 Event connector socket Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in Connector plug Wiring Use the following connector plug as that connected to the event input output connector Connector plug is sold separately SRVP 01 Front screw ...

Page 8: ...action is selectable Specify when ordering Heat cool control is selectable Specify when ordering Additional function Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input DI Number of inp...