IMS01P08-E3
3
(4) Control output (CH1), (5) Control output (CH2)
M: Relay contact output
V: Voltage pulse output 0/12 V DC
4: 0 to 5 V DC
5: 0 to 10 V DC
6: 1 to 5 V DC
7: 0 to 20 mA DC
8: 4 to 20 mA DC
(6) Event input (DI) [Optional]
N: None
1: Control RUN/STOP
2: Event interlock release
(7) (8) Event output 1 (DO1) [Optional]
*
(9) (10) Event output 2 (DO2) [Optional]
*
[(7), (9) code: Channel selection]
N: None
1: Input channel 1
2: Input channel 2
[(8), (10) code: Output type]
N: None
A: Deviation high
B: Deviation low
C: Deviation high/low
D: Band
E: Deviation high with hold action
F: Deviation low with hold action
G: Deviation high/low with hold action
H: Process high
J: Process low
K: Process high with hold action
L: Process low with hold action
Q: Deviation high with re-hold action
R: Deviation low with re-hold action
T: Deviation high/low with re-hold action
P: Heater break alarm
1: Control loop break alarm
2: Burnout
3: Temperature rise completion
(11) CT type
(Each channel common code)
P: CTL-6-P-N
S: CTL-12-S56-10L-N
(12) Communication protocol
1: Modbus/TCP
*
When “N” is selected in (7) or (9), (8) or (10) becomes “N.”
•
For heat/cool PID control (V-TIO-Q), input channel
2 becomes unused.
•
For heat/cool PID control (V-TIO-Q), Control output
(CH1) corresponds to the heating output and
Control output (CH2) corresponds to the cooling
output.
•
Heater break alarm function cannot be used when
control output is voltage/current output.
If any of the products are missing, damaged, or if your
manual is incomplete, please contact RKC sales office
or the agent.
3. PARTS DESCRIPTION
Terminal cover
Indication lamps 1
Address setting
switch
Terminal cover
Indication lamps 2
Event
connector
*
Ethernet communication side Temperature control side
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
Modular connector
for Ethernet
RJ-45
Indication lamp 3
Indication lamp 4
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
[Indication lamps 1]
FAIL/RUN (for temperature control)
When normally:
Green lamp: ON (RUN)
When abnormally:
Red lamp:
ON (FAIL)
During self-diagnostic error:
Green lamp: flashing
RX/TX (for internal communication)
During data send and receive: Green lamp: ON
EVENT 1 to 4
Display various states by setting.
Display contents: Event 1 state, Event 2 state, Comprehensive event state,
Output state, Control state
[Indication lamps 2]
FAIL (for Ethernet communication)
When normally:
Red lamp:
OFF
When abnormally:
Red lamp:
ON
RUN (for Ethernet communication)
When normally:
Green lamp: ON
When abnormally [Module configuration error, input error]:
Green lamp: slow flashing
Data collection just after the power is turned on:
Green lamp: rapid flashing
TX
During data send:
Green lamp: flashing
RX
During data receive:
Green lamp: flashing
[Indication lamps 3]
Link
10BASE-T link:
Amber lamp: ON
100BASE-TX link:
Green lamp: ON
[Indication lamps 4]
Activity
Half-duplex; activity:
Amber lamp: Momentary ON
Full-duplex; activity:
Green lamp: Momentary ON
Accessories
End Plate ................................................................... 2
Joint connector cover................................................. 2
Instruction Manual (IMS01P08-E3) ........................... 1
*
Installed when provided with the event input or output (optional).
Indication
lamp 2
Indication
lamp 1
Temperature control side
Ethernet communication side
FAIL
RUN
T
X
R
X