5. LADDER COMMUNICATION
IM9000F02-E2
37
e
ID [Identifier]
These are numbers used for the PLC to identify data to be requested or set to the REX-
F9000.
These are numbers of four figures in the communication identifier list (P.44).
f
CMD [Command]
These are commands used for the PLC to identify the details of processing and the data sing
to be requested to the REX-F9000.
PLC
o
REX-F9000 (During data send from PLC)
Command
(CMD)
Details
Identifier transfer order
(0000)
0001
Read request
Upper byte
o
Lower byte
0010
Write request, write data +(Positive)
0011
Write request, write data - (Negative)
0100
Read request (Byte inversion)
1000
Write request, write data +(Positive)
Lower byte
o
Upper byte
1100
Write request, write data - (Negative)
Other
Usage inhibited
REX-F9000
o
PLC (During data receive by PLC)
Command
(CMD)
Details
Identifier transfer order
0000
Read response, read data +(Positive)
*
1
0001
Read response, read data - (Negative)
Upper byte
o
Lower byte
0010
Write response, write result data + (Positive)
0011
Write response, write result data - (Negative)
0100
Read response, read data - (Negative)
Lower byte
o
Upper byte
1000
Read request, write result data + (Positive)
1100
Read request, write result data - (Negative)
Other
Abnormal response
*
1
: Data transfer order is in accordance with the command from the PLC connected to the REX-F9000.