IMCB02-E5 5
Parameter table
#1:Factory set value
Symbol
Name
Setting range
Description
#1
Current
transformer
input 1 (CT1)
0.0 to 100.0 A
[Only display]
Display input value from the current
transformer.
[Displayed only when the instrument has
the heater break alarm ]
First alarm
(ALM1)
Second alarm
(ALM2)
For temperature input:
Deviation alarm, Process alarm,
SV alarm:
-1999 to +9999
°
C[
°
F ] or
-199.9 to +999.9
°
C[
°
F ]
For voltage/current inputs:
Deviation alarm :
-span to +span (Within 9999)
Process alarm, SV alarm:
Same as input range
Set the first alarm set value and
second alarm set value.
Alarm differential gap:
Temperature input: 2 or 2.0
°
C[
°
F]
Voltage/current inputs:
0.2 % of span
Temperature
input: 50(50.0)
Voltage/
current inputs:
5.0
Heater break
alarm 1 (HBA)
0.0 to 100.0 A
See *1.
Alarm value is set by referring
to input value from the current
transformer (CT).
Used only for single-phase.
0.0
Control loop
break alarm
(LBA)
0.1 to 200.0 min.
(0.0 can not be set.)
See *2.
Set control loop break alarm
set value.
8.0
LBA deadband
(LBD)
Temperature input:
0 to 9999
°
C[
°
F ]
Voltage/current inputs:
0 to 100 % of span
Set the area of not outputting LBA.
No LBA deadband functions with "0"
set.
Differential gap :
Temperature input 0.8
°
C[
°
F ]
Voltage/current inputs 0.8 % of span
0
Autotuning (AT) 0: AT end or AT suspension
1: AT start
Turns the autotuning ON/OFF.
0
Self-tuning (ST) 0: ST suspension
1: ST start
Turns the self-tuning ON/OFF.
0
Proportional
band (P)
Temperature input:
1(0.1) to span or
9999(999.9)
°
C[
°
F ]
Voltage/current inputs:
1 to 100.0 % of span
Set when PI,PD or PID control is
performed.
For heat/cool PID action: Proportional
band setting on the heat-side.
*ON/OFF action control when set
to "0(0.0)."
Differential gap :
Temperature input 2 or 2.0
°
C[
°
F]
Voltage/current inputs 0.2 % of span
Temperature
input: 30(30.0)
Voltage/
current inputs:
3.0
Integral time
( I )
1 to 3600 sec
*PD control when set to 0 sec.
Set the time of integral action which
eliminates the offset occurring in
proportional control.
240
Derivative time
(D)
1 to 3600 sec
*PI control when set to 0 sec.
Set the time of derivative action
which prevents ripples by predicting
output changes and thus improves
control stability.
60
Anti-reset
windup (ARW)
1 to 100 % of heat-side
proportional band.
*"0" setting: integral action OFF
Overshooting and undershooting
are restricted by the integral effect.
100
Heat-side
proportioning
cycle (T)
1 to 100 sec (0 can not be set.)
*Not displayed if the control
output is current output.
Set control output cycle.
For heat/cool PID action:
Heat-side proportioning cycle
See *3.
Cool-side
proportional
band (Pc)
1 to 1000 % of heat-side
proportional band.
(0 can not be set.)
Set cool-side proportional
band when heat/cool PID action.
100
Deadband (db)
Temperature input:
-10 to +10
°
C[
°
F ] or
-10.0 to +10.0
°
C[
°
F ]
Voltage/current inputs:
-10.0 to +10.0 % of span
Set control action deadband
between heat-side and cool-side
proportional bands.
Minus (-) setting results in overlap.
0 or 0.0
(Continued on the next page. )