3.COMMUNICATION INITIALIZE IDENTIFIER
IMCB10-E1
22
*5
⋅⋅⋅⋅
0 : Alarm 1 (Energized alarm), Alarm 2 (Energized alarm)
1 : Alarm 1 (De-energized alarm), Alarm 2 (Energized alarm)
2 : Alarm 1 (Energized alarm), Alarm 2 (De-energized alarm)
3 : Alarm 1 (De-energized alarm), Alarm 2 (De-energized alarm)
4 : Alarm 1 (Energized alarm, Z-124 specification provided), Alarm 2 (Energized alarm)
5 : Alarm 1 (De-energized alarm, Z-124 specification provided), Alarm 2 (Energized alarm)
6 : Alarm 1 (Energized alarm, Z-124 specification provided), Alarm 2 (De-energized alarm)
7 : Alarm 1 (De-energized alarm, Z-124 specification provided), Alarm 2 (De-energized
alarm)
8 : Alarm 1 (Energized alarm), Alarm 2 (Energized alarm, Z-124 specification provided)
9 : Alarm 1 (De-energized alarm), Alarm 2 (Energized alarm, Z-124 specification provided)
10 : Alarm 1 (Energized alarm), Alarm 2 (De-energized alarm, Z-124 specification provided)
11 : Alarm 1 (De-energized alarm), Alarm 2 (De-energized alarm, Z-124 specification
provided)
12 : Alarm 1 (Energized alarm, Z-124 specification provided),
Alarm 2 (Energized alarm, Z-124 specification provided)
13 : Alarm 1 (De-energized alarm, Z-124 specification provided),
Alarm 2 (Energized alarm, Z-124 specification provided)
14 : Alarm 1 (Energized alarm, Z-124 specification provided),
Alarm 2 (De-energized alarm, Z-124 specification provided)
15 : Alarm 1 (De-energized alarm, Z-124 specification provided),
Alarm 2 (De-energized alarm Z-124 specification provided)
*6
⋅⋅⋅⋅
0 : Limit action [Energized action]
(The limit action is forcibly ON when the burnout function is activated.)
1 : Limit action [De-energized alarm]
(The limit action is forcibly ON when the burnout function is activated.)
2 : Limit action [Energized action]
(No limit action is taken by the burnout function. Same as the normal limit action.)
3 : Limit action [De-energized alarm]
(No limit action is taken by the burnout function. Same as the normal limit action.)
*7
⋅⋅⋅⋅
TC, RTD input : 2 or 2.0
Voltage, current input : 0.2