Rittal SK 3359.xxx Assembly Instructions Manual Download Page 6

 

10

Fig. 9.3  

 

Condensate discharge

 

10. Handling Instructions

 

Storage, maintenance, transport and disposal

 

As a maintenance-free, hermetically sealed 
system, the cooling circuit has been filled in the 
factory with the required amount of refrigerant, 
and tested for leaks and subjected to a function 
trial run.
The installed maintenance-free fans use ball 
bearings, they are protected against moisture and 
dust, and are fitted with a temperature monitor. 
The life expectancy is at least 30,000 operating 
hours. The cooling unit is thus largely mainte-
nance free. All that may be required from time to 
time is that the components of the external air 
circuit are cleaned by compressed air. The use of 
a filter mat is recommended only if large particles 
of lint are present in the air, so that blockage of the 
condenser is prevented. (Filter mat replacement, 
fig. 7.1). Note: Prior to any maintenance work, the 
power to the cooling unit must be disconnected.

Storage temperature: The cooling units must not 
be exposed to temperatures above +70°C.
Transport position: The cooling units must always 
be transported upright.
Waste disposal: The closed cooling circuit 
contains refrigerant and oil which must be 
correctly disposed of for the protection of the 
environment. Disposal can be carried out at 
Rittal. 
We reserve the right to make technical 
modifications.

 

11. Scope of supply and

guarantee

 

1 cooling unit, ready for connection
1 drilling template
1 sealing plate
1 sealing frame
1 set of mounting and operating instructions
1 plug-in terminal strip

Guarantee:
This unit is covered by a 1-year guarantee from the 
date of supply, subject to correct usage (see also 
Safety notices under heading 4.). Within this period, 
the returned unit will be repaired in the factory or 
replaced free of charge. The cooling unit is to be 
used for the cooling of enclosures only. If it is con-
nected or handled improperly the manufacturer’s 
guarantee does not apply and in this case we are 
not liable for any damage caused.

 

1

/

2

′′

 

9. Technical information

 

The cooling unit (compressor refrigeration unit) 
consists of four main components: the coolant 
compressor, evaporator, condenser, and the 
control or expansion valve, which are connected 
by suitable pipework. This circuit is filled with
a readily boiling substance, the refrigerant. The 
R134a (CH

 

2

 

FCF

 

3

 

) refrigerant is free from chlo-

rine. It has an ozone destroying potential (ODP) 
of 0 and is therefore environmentally friendly. A 
filter dryer which is integrated in the hermetically 
sealed cooling circuit, provides effective protec-
tion against moisture, acid, dirt particles, and 
foreign bodies within the cooling circuit.

 

9.1  Operation of the cooling unit

 

Fig. 9.1  

 

Operation of the cooling unit

 

The compressor takes the gaseous refrigerant 
from the evaporator and compresses it to a 
higher pressure in the condenser. During this 
process the temperature of the refrigerant rises 
above the ambient temperature and heat can be 
dissipated to the environment via the surface of 
the condenser. Then the refrigerant is liquefied 
and, by means of a thermostatically controlled 
expansion valve, returned to the evaporator, 
where it evaporates at low pressure. The heat 
required for complete evaporation is drawn from 
the enclosure interior causing it to cool down. 
The cooling cycle is thus completed, the afore-
mentioned process of the heat transfer starts 
afresh.

 

9.2  Safety equipment

 

The cooling circuit of the cooling unit has a 
component-tested, high-pressure monitor to 
EN 12 263, which is set to maximum PS (allowed 
pressure) and operates via an automatic reset 
device in case of recurring pressure drop. Tem-
perature monitoring will prevent the evaporator 
from icing up. If there is a risk of icing up, the 
compressor is switched off and automatically 
switched on again at higher temperatures. 
The refrigerant compressor and the fans are 
equipped with thermal winding protection 
switches against excess current and excess 
temperatures.

 

9.3  Condensate discharge

 

A cast gutter in the evaporator tray ensures that 
any condesate which may form on the evapora-
tor (at high air humidity, low temperatures inside 
the enclosure), is drained away to the right or 
rear of the unit. For this purpose, a length of 
hose should be fitted to one of the two conden-
sate pipe connection pieces (see fig. 9.3). The 
other drain that is not used has to be sealed 
accordingly. The condensate must be able to 
run off freely. If the condensate is to be drained 
off over a greater distance, then care must be 
taken that the hose is free from kinks and a 
check for correct drainage made. Units with a 
comfort controller have an additional conden-
sate alarm.

Fan 2

Fan 1

Compressor

Evaporator

External circuit
Internal circuit

Expansion valve

Thermostat

Filter
dryer

Liquefier

PSA  

monitor

H

 

English

 

03_SK3382_8_11_eng.fm  Seite 10  Freitag, 5. März 2004  4:33 16

Summary of Contents for SK 3359.xxx

Page 1: ...a armarios Montageanleitung Assembly instructions Notice de montage Montage instructie Montageanvisning Istruzioni di montaggio Instrucciones de montaje Umschalten auf Perfektion SK 3382 xxx SK 3359 xxx SK 3383 xxx SK3384 xxx SK 3385 xxx SK3386 xxx SK 3387 xxx 00_Umsch_Ti_SK3382 fm Seite 1 Freitag 5 März 2004 4 24 16 ...

Page 2: ...åltagning Fig 3 1 Dime di foratura Fig 3 1 Recorte del montaje Montageausschnitt SK 3359 SK 3382 Montageausschnitt SK 3383 SK 3384 SK 3385 Montageausschnitt SK 3386 SK 3387 475 260 326 375 597 475 415 420 280 597 415 380 Ø 100 27 490 597 420 390 475 580 520 392 796 692 470 796 538 Ø 150 38 5 580 238 Ø 150 01_SK3382_2_3 fm Seite 2 Freitag 5 März 2004 4 27 16 ...

Page 3: ... 50 60 Hz 3 0 A 3 9 A 10 0 A 10 7 A 10 0 A 10 0 A 100 410 W 520 W 490 W 600 W 750 W 810 W 545 W 590 W R134a 300 g 25 bar 20 55 C 64 dB A IP 54 IP 34 596 x 415 x 375 32 kg SK 3359 110 SK 3359 510 SK 3359 210 SK 3359 610 115 V 50 60 Hz 6 0 A 7 8 A 20 0 A 21 4 A 16 0 A 16 0 A 100 420 W 535 W 500 W 615 W R134a 300 g 20 55 C 64 dB A IP 54 IP 44 34 kg SK 3359 140 SK 3359 540 SK 3359 240 SK 3359 640 400 ...

Page 4: ...nnected up stream at the supply end The fans and compressors built into single and three phase devices are intrinsically safe thermal winding protection This also applies to SK 3382 SK 3359 SK 3383 SK 3384 SK 3385 transformer types and to specially rated units which are also fitted with a transformer Line protection should be provided by means of the pre fuse specified on the rating plate Only one...

Page 5: ... monitor The filter mat is monitored for soiling by measur ing the temperature difference in the external cir culation of the cooling unit see diagram 13 1 Programming on page 45 In the event of any filter mat soiling the temperature difference will increase The nominal value of the temperature difference in the external circuit is matched to the relevant operating points in the characteristic fie...

Page 6: ...erant The R134a CH2FCF3 refrigerant is free from chlo rine It has an ozone destroying potential ODP of 0 and is therefore environmentally friendly A filter dryer which is integrated in the hermetically sealed cooling circuit provides effective protec tion against moisture acid dirt particles and foreign bodies within the cooling circuit 9 1 Operation of the cooling unit Fig 9 1 Operation of the co...

Page 7: ... be reset manually To do this hold down the and keys simultaneously for 5 seconds 13 Comfort control programming Level Display screen changeable parameter min value max value Factory setting Explanation 1 St Nominal value of the internal enclosure 20 55 35 The nominal value of the internal enclosure temperature is set at the factory to 35 C and is variable over a 20 C range to 55 C 2 Fi Filter mat...

Page 8: ...arning sensor C1 C4 Operating capacitors F2 PSAH monitor F3 Compressor thermal contact K1 Relay collective fault 1 K2 Relay collective fault 2 L1 Green operating LED L2 Red alarm LED M1 Compressor M2 Condenser fan 1 M3 Condenser fan 2 M4 Evaporator fan R1 Setpoint adjustment potentiometer S1 Door limit switch without door operated switch terminal 1 2 open T1 Transformer X1 Main terminal strip X2 M...

Page 9: ...F3 C1 M2 M 1 C2 M1 1 A3 2 3 R C A1 K2 K1 MS1 NTC C NTC A Term Serial 21 22 3 8 2 X2 X3 2 2 2 2 4 B3 B4 B5 C4 M2 1 2 3 M4 1 2 3 R nur bei 3385 xxx 37 Anschlussschema Wiring diagram Schéma électrique Aansluitschema Anslutningsschema Schema allacciamenti Esquema de conexiones Kontaktdaten K1 Contact Data K1 Caracteristiques des contacts K1 Kontaktgegevens K1 Kontaktdata K1 Caratteristiche dei contatt...

Page 10: ... PE 5 Power Kx M1 1 2 3 P M 3 R S C X1 22 21 L2 L3 R S T 3 4 F3 1 2 3 4 M2 1 2 3 4 F4 1 2 3 M4 1 2 3 F5 1 2 F2 M2 M 3 M3 M 3 M4 NTC I NTC E Level A2 2 B1 B2 NTC C NTC A Term 2 2 2 2 4 B3 B4 B5 X2 X3 3 8 S1 K2 K1 Serial MS1 Netz S1 A1 M1 F2 38 Anschlussschema Wiring diagram Schéma électrique Aansluitschema Anslutningsschema Schema allacciamenti Esquema de conexiones Kontaktdaten K1 Contact Data K1 ...

Page 11: ...Controllo PSAH Presostato PSAH 40 Controller Box Controller box Processeur box Controller E box Kontroll box Box controller Carcasa controlador 45 Lamellengitter 1 Louvred grille 1 Grille à lamelles 1 Rooster 1 Lamellgaller 1 Griglia a lamelle 1 Rejilla 1 46 Lamellengitter 2 Louvred grille 2 Grille à lamelles 2 Rooster 2 Lamellgaller 2 Griglia a lamelle 2 Rejilla 2 50 Abdeckblende Infill panel Pla...

Page 12: ...40 40 75 30 1 80 15 25 10 90 20 70 95 45 55 71 100 5 SK 3382 xxx SK 3359 xxx ...

Page 13: ...41 15 95 25 20 45 55 100 75 30 90 5 71 10 70 80 1 40 SK 3383 xxx SK 3384 xxx SK 3385 xxx 10_SK3382_36_47 fm Seite 41 Freitag 5 März 2004 4 51 16 ...

Page 14: ...42 25 5 90 55 95 75 30 71 20 10 15 70 100 1 45 40 SK 3386 xxx SK 3387 xxx ...

Page 15: ...ster slave aansluiting SUB D 9 polig X3 Seriële interface SUB D 9 polig St Connector SUB D 9 polig Bu Bus SUB D 9 polig D GB F NL Beskrivning Master aggregatets adress är beroende på antalet anslutna Slave aggregat 09 Master med 9 Slave agg Slave aggregatets adress börjar alltid med 1 Den 2 siffran visar slave enhetens adress Maximalt 9 Slave aggregat kan kopplas upp till en master varvid varje ag...

Page 16: ...ömbrytare Armadio doppia porta con due interruttori porta Armario de distribución de 2 puertas con dos interruptores de puerta Verdrahtungsbeispiel Türendschalter und Master Slave Betrieb Wiring example Door limit switch and master slave operation Schéma de câblage typique Interrupteur de porte et régime maître esclave Bekabelingsvoorbeeld deurschakelaar en master slave functie Kopplingsexempel Dö...

Page 17: ... 30 35 40 45 55 QK Tu Ti 7000 6000 5000 4000 3000 2000 1000 20 25 30 35 45 40 50 55 20 30 40 55 QK Tu Ti 1050 900 750 600 450 300 150 0 20 25 30 35 45 40 50 55 20 25 30 35 40 45 55 QK Tu Ti 2000 1750 1500 1250 1000 750 500 250 20 25 30 35 45 40 50 55 20 25 30 35 40 45 55 QK Tu Ti 3000 2600 2200 1800 1400 1000 600 400 20 25 30 35 45 40 50 55 20 25 30 35 40 45 50 55 QK Tu Ti 4000 3500 3000 2500 2000...

Page 18: ...ierung Diagram 13 1 Programming Diagramme 13 1 Programmation Diagram 13 1 Programmering Diagram 13 1 Programering Diagramma 13 1 Programmazione Diagrama 13 1 Programación 10_SK3382_36_47 fm Seite 46 Freitag 5 März 2004 4 51 16 ...

Page 19: ...ling EL Sistemi di allestimento per l elettronica industriale EL Sistemas para electrónica EL Power Distribution SV IT Solutions IT Solutions Communication Systems CS Communication Systems CS System Climate Control SK Stromverteilung SV System Klimatisierung SK Distribution du courant SV Stroomverdeling SV Strömfördelning SV Distribuzione di corrente SV Distribución de corriente SV Solutions IT IT...

Reviews: