Rittal SK 3359.xxx Assembly Instructions Manual Download Page 5

 

9

After electrical connection the internal fan turns on 
and circulates the enclosure air. This helps assure 
even temperature distribution within the enclosure. 
The condenser fan and compressor are controlled 
by the Comfort controller. The minimum break time 
is 3 min. The switching difference is 5 K, but 
can be set in the range 2 – 10 K. To avoid short 
switching cycles and hence the danger of 
inadequate or only partial cooling in some 
sections of the enclosure, the switching difference 
should be set to be only as low as necessary. 
For economic reasons (energy saving), the 
nominal value of the internal enclosure 
temperature T

 

i

 

 should also be set to be only 

as low as necessary.

 

6.2.1 Operation of the Comfort controller

(see  diagram 13.1 Programming)

 

The display terminal H1 consists of a 3 position
7-segment display which indicates the enclosure 
internal temperature in °C or °F (changeable) as 
well as any fault codes. The actual enclosure 
internal temperature is constantly displayed on 
H1. When a system message is generated, this 
alternates in the display with the current internal 
enclosure temperature. While programming the 
unit, the programming level and prescribed value 
are also displayed.

 

Test mode

 

By simultaneously holding down keys H2 
(

 

 

°C key) and H4 (

/set key) for 5 seconds, the 

cooling unit will commence cooling operation, 
irrespective of the setpoint. The door limit switch 
function is disregarded in such cases. After 
approximately 5 minutes or upon reaching 15°C, 
the device deactivates cooling operation once 
again.

 

6.2.2 Programming

(see  13.1 Comfort controller
programming)

 

In the EEPROM of the Comfort controller various 
parameters are stored which can be changed by 
using the buttons H2, H3 and H4. 24 changeable 
parameters can be set via 24 programme levels in 
the stated ranges (max. and min. values). 
To this end, input code “22” is required 
(see diagram 13.1).
The H2, H3 and H4 keys are multiple occupancy. 
To access programming mode, set 5 sec is to be 
pressed and held down.
Primary occupancy (only diode displays):
H2: °C, H3: °F, H4: Alarm
Secondary occupancy (for programming):
H2: Arrow upwards, H3: Arrow downwards, 
H4: set
Programming via diagnostic software (order no. 
SK 3159.100) is also an option. The programming 
cable interface is the connecting cable  plug, 
located on the rear of the Comfort controller. To do 
this, the louvred grille also is to be removed if 
necessary.

 

6.2.3  System messaging equipment

 

All system messages at the cooling unit are 
recorded and displayed as an error number 
by H1. System messages alternate in the display 
with the current internal enclosure temperature.
(see 12. Comfort control fault display and error 
analysis).

 

6.2.3.1 System message contacts

(K1 and K2; potential free)

 

Both relays are normally closed.
All system messages assigned to an individual 
relay result in it opening. If the control voltage 
fails, this also results in the relay opening and can 
hence be captured and documented in the log 
file. According to individual weighting, all system 
messages can be assigned to both relays or 
suppressed. Terminal strip X3 provides the 
connection. See the wiring diagram for contact 
data and occupancy.
K1/K2 fault signal relay (normally open contact):
Terminal 3: Fault signal relay 1
Terminal 4: Voltage supply connection for both

fault signal relays

Terminal 5: Fault signal relay 2
(see the circuit diagrams on page 37).

 

7. Supplementary functions

 

7.1  Filter mat use and changing

 

The PU foam filter mat available as an accessory 
is coarse and filters large dust particles or fluff 
from the air. Metallic filter mats are used to trap 
oil condensate. These are also available as an 
accessory. Subject to the suction of the blower 
being high enough, fine dust is  blown through 
the filter mat and the external circuit of the unit. 
This does not affect the unit's operation.

Fig.7.1  

 

Filter mat replacement

7.2  Filter mat monitoring

 

Function of the filter mat monitor:
The filter mat is monitored for soiling by measur-
ing the temperature difference in the external cir-
culation of the cooling unit (see diagram 13.1: 
Programming on page 45). In the event of any 
filter mat soiling, the temperature difference will 
increase. The nominal value of the temperature 
difference in the external circuit is matched to the 
relevant operating points in the characteristic 
fields. Hence there is no requirement to adjust the 
nominal value for different unit operating points.

 

7.3  Door limit switch S1 

 (supplied by customer)

 

Where a door limit switch is used and the enclo-
sure door is open (contact is closed when door is 
open), the cooling unit (fans and condenser) will 
switch off after approx. 15 s. This only applies to 
devices with a Comfort controller and devices 
with a three-phase connection to the basic con-
troller. For devices with a basic controller (115 V, 
230 V and 400 V, 2~), the internal fan is not 
switched off when using a door limit switch. 
Thereby avoiding an increase in condensation 
while the door is open. To avoid cyclic operation, 
switch-on of condenser and external fan is 
delayed by about 3 minutes after the cooling unit 
has been switched off.
The internal fan will start up after about 15 s on 
closure of the door. Connection is made at the 
terminals 1 and 2. The extra low voltage is 
supplied by the internal power pack, current is 
approx. 30 mA DC. Each door limit switch must 
only be assigned to one cooling unit. Several door 
limit switches may be operated on one cooling 
unit (parallel connection). The minimum cross-
section of the connection cable is 0.3 mm

 

2

 

 for a 

cable length of 2 m. The resistance of the door 
limit switch contact must not exceed a maximum 
of 50

 

 

.

 

Only connect the door limit switch to the 
cooling unit’s own DC supply!

7.4 Interface X3 (option)

(Connector X3)

Note!

 

The electrical signals at the interface are of an 
extra-low voltage (not extra-low safety voltages
to EN 60 335).

The 9-pin SUB-D socket X3 can be used to 
connect additional interface cards for integrating 
cooling units with higher level monitoring systems. 
These cards are also available as an accessory.
(Interface card: Model No. SK 3124.200).

1.

2.

 

8. BUS system

 

(Model No.: Master-slave cable SK 3124.100)

 

8.1  General

 

The BUS system allows a maximum of 10 cool-
ing units to be interconnected.
As a result, the following functions are available 
to the operator:

 

 

Parallel unit control (the cooling units in the
network can be simultaneously switched
on and off)

 

 

Parallel door status messages (“door open”)

 

 

Parallel collective fault message

The data exchange is carried out using master-
slave cables (shielded, two-wire leads). All units 
are assigned an address. This address also 
includes the ID for “master” or “slave”.

 

8.2 Installation notices for the X2 interface

(Jack X2)

Note!

 

The electrical signals at the interface are of an 
extra-low voltage (not extra-low safety voltages 
to EN 60 335). Always heed the following notes!

 

 

De-energise the cooling units to be 
connected.

 

 

Ensure proper electrical insulation. 

 

 

Make sure the cables are not laid in parallel 
to power lines.

 

 

Make sure that the lines are short.

 

8.3 Programming the cooling unit

 

See diagram 13.1 for details on programming.

ID’s:

 

Note

 

Only one unit may be configured as master; the 
address ID must match the number of slave 
units.
The individual slave units must have different 
addresses; the addresses must be in ascending 
order (without gaps in between).

Example: 
1 master cooling unit with 2 slave cooling units

(see wiring example of master/slave and door 
limit function, page 42/43).

Master cooling unit

Slave cooling unit

00

Basic state

00

Basic state

01

Master 

with 1 slave

11

Slave 

with address 1

02

Master 

with 2 slaves

12

Slave 

with address 2

03

Master 

with 3 slaves

13

Slave 

with address 3

04

Master 

with 4 slaves

14

Slave 

with address 4

05

Master 

with 5 slaves

15

Slave 

with address 5

06

Master 

with 6 slaves

16

Slave 

with address 6

07

Master 

with 7 slaves

17

Slave 

with address 7

08

Master 

with 8 slaves

18

Slave 

with address 8

09

Master 

with 9 slaves

19

Slave 

with address 9

Master 

02 

Slave 

11 

Slave 

12 

 

03_SK3382_8_11_eng.fm  Seite 9  Freitag, 5. März 2004  4:33 16

Summary of Contents for SK 3359.xxx

Page 1: ...a armarios Montageanleitung Assembly instructions Notice de montage Montage instructie Montageanvisning Istruzioni di montaggio Instrucciones de montaje Umschalten auf Perfektion SK 3382 xxx SK 3359 xxx SK 3383 xxx SK3384 xxx SK 3385 xxx SK3386 xxx SK 3387 xxx 00_Umsch_Ti_SK3382 fm Seite 1 Freitag 5 März 2004 4 24 16 ...

Page 2: ...åltagning Fig 3 1 Dime di foratura Fig 3 1 Recorte del montaje Montageausschnitt SK 3359 SK 3382 Montageausschnitt SK 3383 SK 3384 SK 3385 Montageausschnitt SK 3386 SK 3387 475 260 326 375 597 475 415 420 280 597 415 380 Ø 100 27 490 597 420 390 475 580 520 392 796 692 470 796 538 Ø 150 38 5 580 238 Ø 150 01_SK3382_2_3 fm Seite 2 Freitag 5 März 2004 4 27 16 ...

Page 3: ... 50 60 Hz 3 0 A 3 9 A 10 0 A 10 7 A 10 0 A 10 0 A 100 410 W 520 W 490 W 600 W 750 W 810 W 545 W 590 W R134a 300 g 25 bar 20 55 C 64 dB A IP 54 IP 34 596 x 415 x 375 32 kg SK 3359 110 SK 3359 510 SK 3359 210 SK 3359 610 115 V 50 60 Hz 6 0 A 7 8 A 20 0 A 21 4 A 16 0 A 16 0 A 100 420 W 535 W 500 W 615 W R134a 300 g 20 55 C 64 dB A IP 54 IP 44 34 kg SK 3359 140 SK 3359 540 SK 3359 240 SK 3359 640 400 ...

Page 4: ...nnected up stream at the supply end The fans and compressors built into single and three phase devices are intrinsically safe thermal winding protection This also applies to SK 3382 SK 3359 SK 3383 SK 3384 SK 3385 transformer types and to specially rated units which are also fitted with a transformer Line protection should be provided by means of the pre fuse specified on the rating plate Only one...

Page 5: ... monitor The filter mat is monitored for soiling by measur ing the temperature difference in the external cir culation of the cooling unit see diagram 13 1 Programming on page 45 In the event of any filter mat soiling the temperature difference will increase The nominal value of the temperature difference in the external circuit is matched to the relevant operating points in the characteristic fie...

Page 6: ...erant The R134a CH2FCF3 refrigerant is free from chlo rine It has an ozone destroying potential ODP of 0 and is therefore environmentally friendly A filter dryer which is integrated in the hermetically sealed cooling circuit provides effective protec tion against moisture acid dirt particles and foreign bodies within the cooling circuit 9 1 Operation of the cooling unit Fig 9 1 Operation of the co...

Page 7: ... be reset manually To do this hold down the and keys simultaneously for 5 seconds 13 Comfort control programming Level Display screen changeable parameter min value max value Factory setting Explanation 1 St Nominal value of the internal enclosure 20 55 35 The nominal value of the internal enclosure temperature is set at the factory to 35 C and is variable over a 20 C range to 55 C 2 Fi Filter mat...

Page 8: ...arning sensor C1 C4 Operating capacitors F2 PSAH monitor F3 Compressor thermal contact K1 Relay collective fault 1 K2 Relay collective fault 2 L1 Green operating LED L2 Red alarm LED M1 Compressor M2 Condenser fan 1 M3 Condenser fan 2 M4 Evaporator fan R1 Setpoint adjustment potentiometer S1 Door limit switch without door operated switch terminal 1 2 open T1 Transformer X1 Main terminal strip X2 M...

Page 9: ...F3 C1 M2 M 1 C2 M1 1 A3 2 3 R C A1 K2 K1 MS1 NTC C NTC A Term Serial 21 22 3 8 2 X2 X3 2 2 2 2 4 B3 B4 B5 C4 M2 1 2 3 M4 1 2 3 R nur bei 3385 xxx 37 Anschlussschema Wiring diagram Schéma électrique Aansluitschema Anslutningsschema Schema allacciamenti Esquema de conexiones Kontaktdaten K1 Contact Data K1 Caracteristiques des contacts K1 Kontaktgegevens K1 Kontaktdata K1 Caratteristiche dei contatt...

Page 10: ... PE 5 Power Kx M1 1 2 3 P M 3 R S C X1 22 21 L2 L3 R S T 3 4 F3 1 2 3 4 M2 1 2 3 4 F4 1 2 3 M4 1 2 3 F5 1 2 F2 M2 M 3 M3 M 3 M4 NTC I NTC E Level A2 2 B1 B2 NTC C NTC A Term 2 2 2 2 4 B3 B4 B5 X2 X3 3 8 S1 K2 K1 Serial MS1 Netz S1 A1 M1 F2 38 Anschlussschema Wiring diagram Schéma électrique Aansluitschema Anslutningsschema Schema allacciamenti Esquema de conexiones Kontaktdaten K1 Contact Data K1 ...

Page 11: ...Controllo PSAH Presostato PSAH 40 Controller Box Controller box Processeur box Controller E box Kontroll box Box controller Carcasa controlador 45 Lamellengitter 1 Louvred grille 1 Grille à lamelles 1 Rooster 1 Lamellgaller 1 Griglia a lamelle 1 Rejilla 1 46 Lamellengitter 2 Louvred grille 2 Grille à lamelles 2 Rooster 2 Lamellgaller 2 Griglia a lamelle 2 Rejilla 2 50 Abdeckblende Infill panel Pla...

Page 12: ...40 40 75 30 1 80 15 25 10 90 20 70 95 45 55 71 100 5 SK 3382 xxx SK 3359 xxx ...

Page 13: ...41 15 95 25 20 45 55 100 75 30 90 5 71 10 70 80 1 40 SK 3383 xxx SK 3384 xxx SK 3385 xxx 10_SK3382_36_47 fm Seite 41 Freitag 5 März 2004 4 51 16 ...

Page 14: ...42 25 5 90 55 95 75 30 71 20 10 15 70 100 1 45 40 SK 3386 xxx SK 3387 xxx ...

Page 15: ...ster slave aansluiting SUB D 9 polig X3 Seriële interface SUB D 9 polig St Connector SUB D 9 polig Bu Bus SUB D 9 polig D GB F NL Beskrivning Master aggregatets adress är beroende på antalet anslutna Slave aggregat 09 Master med 9 Slave agg Slave aggregatets adress börjar alltid med 1 Den 2 siffran visar slave enhetens adress Maximalt 9 Slave aggregat kan kopplas upp till en master varvid varje ag...

Page 16: ...ömbrytare Armadio doppia porta con due interruttori porta Armario de distribución de 2 puertas con dos interruptores de puerta Verdrahtungsbeispiel Türendschalter und Master Slave Betrieb Wiring example Door limit switch and master slave operation Schéma de câblage typique Interrupteur de porte et régime maître esclave Bekabelingsvoorbeeld deurschakelaar en master slave functie Kopplingsexempel Dö...

Page 17: ... 30 35 40 45 55 QK Tu Ti 7000 6000 5000 4000 3000 2000 1000 20 25 30 35 45 40 50 55 20 30 40 55 QK Tu Ti 1050 900 750 600 450 300 150 0 20 25 30 35 45 40 50 55 20 25 30 35 40 45 55 QK Tu Ti 2000 1750 1500 1250 1000 750 500 250 20 25 30 35 45 40 50 55 20 25 30 35 40 45 55 QK Tu Ti 3000 2600 2200 1800 1400 1000 600 400 20 25 30 35 45 40 50 55 20 25 30 35 40 45 50 55 QK Tu Ti 4000 3500 3000 2500 2000...

Page 18: ...ierung Diagram 13 1 Programming Diagramme 13 1 Programmation Diagram 13 1 Programmering Diagram 13 1 Programering Diagramma 13 1 Programmazione Diagrama 13 1 Programación 10_SK3382_36_47 fm Seite 46 Freitag 5 März 2004 4 51 16 ...

Page 19: ...ling EL Sistemi di allestimento per l elettronica industriale EL Sistemas para electrónica EL Power Distribution SV IT Solutions IT Solutions Communication Systems CS Communication Systems CS System Climate Control SK Stromverteilung SV System Klimatisierung SK Distribution du courant SV Stroomverdeling SV Strömfördelning SV Distribuzione di corrente SV Distribución de corriente SV Solutions IT IT...

Reviews: