Rittal enclosure cooling unit
19
5 Installation
EN
At the bottom, screw two grub screws into the blind
rivet nuts in the front corners of the cooling unit (torque
= 5 Nm).
Fig. 32:
Screw the bottom grub screws into place
Lift up the cooling unit, and set it down initially with the
two inside lower grub screws resting on the enclosure
door or side panel.
Fig. 33:
Position the cooling unit and push it into place
For SK 317880x and SK 317980x: Push the cooling
unit into the mounting cut-out at the top until the clip
behind the cut-out audibly latches home.
Fig. 34:
Latch home the clip behind the cut-out (for SK
317880x and SK 317980x)
For SK 31848x0: Push the cooling unit into the mount-
ing cut-out at the top until the clips behind the cut-out
audibly latch home.
Fig. 35:
Lock home the clips behind the cut-out (for
SK 31848x0)
Similarly, at the top, screw two grub screws into the
blind rivet nuts at the front corners of the cooling unit
(torque = 5 Nm).
Fig. 36:
Screw the top grub screws into place
Attach the two corner brackets with nuts to the
threaded grub screws at the top and secure (torque =
5 Nm).
Fig. 37:
Secure with corner brackets at the top
CLICK!
CLICK!
CLICK!