background image

 

 

Commissioning 7 

CMC-TC Wireless I/O-Unit 

9

EN 

 

 

 

Fig. 9 

Unit detection browser window 

Key 

Status display of the sensor island 

The "Unit detected" message appears in the 
browser window of the Processing Unit. 

Continue to press the 

C key

 on the Processing Unit 

until the Status LED of the CMC-TC Wireless I/O-
Unit switches to a continuous green. 

 

 

Fig. 10 

Overview display browser window 

 

Key 

Overview display 

Status of the I/O-Unit 

Clear button 

The CMC-TC Wireless I/O-Unit has now been de-
tected. 

 

7.2  Registering Sensors 

 

Fig. 11  Wireless I/O-Unit (programming status) 

Key 

C key 

Wireless connection LED 

Press the 

C key

 on the Wireless I/O-Unit for three 

seconds. The wireless connection LED now flashes 
alternately red, yellow and green. The CMC-TC 
Wireless I/O-Unit is now in programming mode. 

 

Fig. 12  Wireless sensor (lower side) 

Key 

Status LED 

Micro pushbutton 

Press the Sensor micro-pushbutton (Push) located 
on the lower side one second. The Status LED on 
the sensor illuminates once briefly. If the registration 
process was successful, the Wireless Connection 
LED of the CMC-TC Wireless I/O-Unit flashes green 
for approximately two seconds, then alternately red, 
yellow, green. Simultaneously, the Status LED on 
the CMC-TC Wireless I/O-Unit flashes alternately 
red, yellow and green. 

 

 

 

Note!

 

During the registration process, the dis-
tance between the sensor and the Wire-
less I/O-Unit may not exceed 5 m, be-
cause the I/O-Unit operates with reduced 
transmission power in this mode. 

No other I/O-Unit within a 5 m range must 
be in registration mode during the regis-
tration process. 

 

 

Note!

 

For the commissioning of the sensors, 
please observe information provided in 
the Wireless Sensors manual. 

 

 

Fig. 13 

Sensor identification 

Key 

Status display of the sensor island 

Clear button 

 

"Configuration changed" appears in the browser 
window. Press the 

Clear

 button (possibly several 

times). The sensor is now registered to the I/O-Unit. 
To test the registration, click in the overview display 
the name of the I/O-Unit (here: CMC-TC-IOW). The 
overview of the registered sensors is now displayed. 

Summary of Contents for DK 7320.240

Page 1: ...EN CMC TC Wireless I O Unit DK 7320 240 Assembly Installation and Operation A38148 11 IT 74 ...

Page 2: ...H 45504 Telefon 1 937 399 05 00 Fax 1 937 390 55 99 eMail rittal rittal corp com Website www rittal corp com Published 03 11 2008 Microsoft Windows is a registered trademark of Microsoft Corporation Acrobat Reader is a registered trademark of Adobe Systems Incorporated ...

Page 3: ...mming Mode 11 7 5 Tips and Notes for the Sensor Placement 11 7 5 1 Tips for the Calibration of the Sensor Locations 11 7 5 2 Introduction to the Wireless Data Transmission for the Rittal Wireless Sensor Network 12 7 5 3 Wireless System Range Estimate 13 7 5 4 Troubleshooting 14 8 Operation 15 8 1 Access Using a Browser 15 8 1 1 Login Using a Browser 15 8 1 2 Main Page View 15 8 1 3 General Overvie...

Page 4: ...t in particular for wiring the enclo sures with mains power may be performed only by a trained electrician Other tasks associated with the CMC TC Wireless I O Unit such as the assembly and installation of system components with tested standard connectors and the opera tion and configuration of the CMC TC Wireless I O Unit may be performed only by instructed personnel Observe the valid regulations ...

Page 5: ...ation change Flashing red System is in reset 3 Wireless connection LED Off No operating voltage is present Green Normal operation Green interrupted briefly for some time ms a data package is being sent Orange System is in repeater mode Red System in repeater mode has lost the base station Flashing red System is in reset Flashing green orange red System is in the log in mode 1 2 3 Fig 2 CMC TC Wire...

Page 6: ...or Country version USA CDN UL approval FT1 VW1 1 7200 214 Connec tion cable for power pack Extension cable IEC connector and socket 1 Yes once for power pack 7200 215 1 U mounting unit 1 7320 440 Assem bly 1 U single moun ting unit with strain relief 1 Optional 7320 450 RJ45 0 5 m 7320 470 RJ45 2 0 m 7320 472 Connec tion cable RJ45 5 0 m 1 1 7320 475 Tab 3 Required accessories 4 5 2Optional Access...

Page 7: ...te of the mounting module Ensure that the retaining plate sits between the guide rails of the CMC TC Wireless I O Unit Fig 4 Assembly with Velcro fasteners Take the self adhesive Velcro fasteners from the supplied accessories and remove the protective foil from the Velcro fasteners Ensure that the adhesion surfaces are free from grease and dust Attach the Velcro fasteners to the housing of the CMC...

Page 8: ...tion 4 5 1 Required Accessories Insert the plug connector of the RJ45 connection cable in the socket as shown above of the CMC TC Wireless I O Unit Power 24 VDC max 2 5 A I0I0I 1 P I C 2 1 2 4 3 1 Fig 7 Connecting to the CMC TC Processing Unit with software version as of V 2 46 Key 1 CMC TC units connection Insert the other end of the RJ45 connection cable in a free RJ45 socket with number 1 to 4 ...

Page 9: ...de one second The Status LED on the sensor illuminates once briefly If the registration process was successful the Wireless Connection LED of the CMC TC Wireless I O Unit flashes green for approximately two seconds then alternately red yellow green Simultaneously the Status LED on the CMC TC Wireless I O Unit flashes alternately red yellow and green Note During the registration process the dis tan...

Page 10: ...ve seconds until the Status LED flashes very quickly To perform an immediate removal switch off the sensor as described above On the configuration page in your web browser switch to the sensor configuration To do this click first in the main overview on the sensor island I O Unit to which the sensor to be removed is connected Fig 15 You must be logged in as administrator to use this function 1 Fig...

Page 11: ...h sensor location must be tested in advance using the wireless meas uring system sensor DK 7320 242 Procedure i Place the I O Unit into operation at the planned location as described in Section 7 1 Tip Before starting the calibration succes sively connect all sensors to the I O Unit This causes the sensors to be placed in front of the measuring system sensor in the registration list of the Process...

Page 12: ...propriate for light If you follow this model it becomes clear that a di rect line of sight connection between the base and the sensor is the most favourable installation vari ant Walls furnishings etc in the vicinity can how ever act as a mirror that reflects the signal like light In this case not only the original signal but also reflected signals from various directions arrive at the receiving p...

Page 13: ...se values are highly dependent on the ambient reflection Enclosure suite for steel door closed up to 6m for steel door 70 vented up to 20m for glazed door up to 30m Enclosure suite side for steel door closed up to 6m for steel door 70 vented up to 10 m for glazed door up to 10 m Note These values are highly dependent on the ambient reflection Adjoining room masonry thickness 30 cm concrete for ste...

Page 14: ...ter present Test the wireless link using the wireless meas uring system Display value should be 8 9 in the vicinity of the I O Unit If necessary rectify the interfering transmitter Sensor is sometimes not received Sensor lies in the fringe range of the I O Unit Test the wireless link using the wireless meas uring system If the display value is smaller than 8 change the installation location or use...

Page 15: ...utton To clear the input click the Clear button 8 1 2Main Page View 1 2 3 4 5 6 7 8 9 Fig 22 Main page overview Key 1 Address bar 2 Status window 3 IP address of the Processing Unit 4 Link to the main page view 5 Setup link 6 Log link 7 Administration link 8 User name 9 User logout 8 1 3General Overview Status Win dow 1 2 4 3 5 6 Fig 23 I O Units overview Key 1 Connection number and type of the I ...

Page 16: ...uler 7 Enter here the numbers 1 to 4 of the mobile wire less numbers that should receive an SMS when an alarm is issued To create the mobile wireless numbers please consult the operating manual of the CMC TC Processing Unit The numbers must be entered separated by an character e g 1 2 3 4 8 Enter here the numbers 1 to 4 of the email adress that should receive an email when an alarm is is sued To c...

Page 17: ...has al ready been registered at a different I O Unit you have to reset the repeater first To reset please press c key for 10 seconds until the status LED is flashing Press for two seconds the C key on the Wireless I O Unit master The wireless connection LED flashes red yellow and green You are now in programming mode Now go to the Repeater Wireless I O Unit and press once the C key You now receive...

Page 18: ... I O Unit as Repeater Hoplist example Fig 30 Hoplist example repeater The humidity sensor was registered on tab 2 The removed CMC TC Wireless I O Unit repeater on tab 3 You see the following message in the hop list Fig 31 Hoplist repeater This means that the signals of the CMC TC wire less humidity sensor on tab 2 using the CMC TC Wireless I O Unit repeater on tab 3 go to the CMC TC Wireless I O U...

Page 19: ...r product spectrum contact the following service address Tel 49 0 2772 505 1855 http www rimatrix5 com E mail info rittal de Note To allow us to process your enquiry quickly and correctly please always specify the article number in the subject line for e mails Further information and the current operating manuals and updates of the Rittal CMC TC can be downloaded from http www rimatrix5 de s ervic...

Page 20: ...MCBASE0108V2 Statement according to FCC part 15 21 Modifications not expressly approved by this company could void the user s authority to oper ate the equipment Statement according to FCC part 15 105 Note This equipment has been tested and found to comply with the limits for a Class A digital de vice pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protec tion ...

Reviews: