4 Assembly and siting
EN
14
Rittal Micro Data Center Level E
Rittal Micro Data Center Level E, 47 U, 1200 mm interior depth with two single-leaf doors
Components
Weight [kg]
Average surface load assuming a total weight of
1340 kg (based on one Micro Data Center)
Mico Data Center Level E
800
Line a.)
437 kg/m²
on a bare floor
TS-IT rack
90
Climate control unit
(LCP is not considered)
150
Live load
300
Line b.)
868 kg/m²
directly below the Micro Data Center sur-
face for floating floors or surface coverings, etc.
Total weight
1340
Rittal Micro Data Center Level E, 47 U, 1200 mm interior depth with two double-leaf doors
Components
Weight [kg]
Average surface load assuming a total weight of
1340 kg (based on one Micro Data Center)
Micro Data Center Level E
800
Line a.)
566 kg/m²
on a bare floor
TS-IT rack
90
Climate control unit
(LCP is not considered)
150
Live load
300
Line b.)
868 kg/m²
directly below the Micro Data Center sur-
face for floating floors or surface coverings, etc.
Total weight
1340
Danger of collapse
The failure of the building structure can
cause severe injuries and death.
Prior to the assembly of the Micro Data
Center, check the requirements placed
on the building statics.
The Micro Data Center may be posi-
tioned only where the building structure
is dimensioned adequately.