11 Technical specifications
EN
30
Rittal LCU DX
11.4.1 LCU DX 3 kW
Exterior temperature [°C]
-18
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.00
1.00
3.00
1.00
3.00
Power consumption [kW]
0.41
0.64
0.46
0.65
0.45
0.68
Tab. 9:
Exterior temperature -18°C
Exterior temperature [°C]
-5
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.00
1.00
3.20
1.00
3.50
Power consumption [kW]
0.46
0.57
0.46
0.66
0.46
0.68
Tab. 10: Exterior temperature -5°C
Exterior temperature [°C]
10
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.50
1.00
3.50
1.00
3.50
Power consumption [kW]
0.43
0.62
0.45
0.69
0.48
0.68
Tab. 11: Exterior temperature 10°C
Exterior temperature [°C]
20
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.50
1.00
3.50
1.00
3.50
Power consumption [kW]
0.49
0.99
0.46
1.05
0.49
0.68
Tab. 12: Exterior temperature 20°C
Exterior temperature [°C]
35
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.50
1.00
3.50
1.00
3.50
Power consumption [kW]
1.00
1.35
0.62
1.43
0.62
0.68
Tab. 13: Exterior temperature 35°C
Exterior temperature [°C]
44
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
1.00
3.50
1.00
3.50
1.00
3.50
Power consumption [kW]
1.02
1.45
0.97
1.52
0.97
0.68
Tab. 14: Exterior temperature 44°C