Rittal LCU DX
31
11 Technical specifications
EN
11.4.2 LCU DX 6.5 kW
Exterior temperature [°C]
-18
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
6.50
3.00
6.50
3.00
6.50
Power consumption [kW]
1.45
2.03
1.66
2.10
1.52
2.10
Tab. 15: Exterior temperature -18°C
Exterior temperature [°C]
-5
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
6.50
3.00
6.50
3.00
6.50
Power consumption [kW]
1.65
2.10
1.48
2.10
1.60
2.10
Tab. 16: Exterior temperature -5°C
Exterior temperature [°C]
10
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
6.50
3.00
6.50
3.00
6.50
Power consumption [kW]
1.57
2.06
1.53
2.18
1.66
2.18
Tab. 17: Exterior temperature 10°C
Exterior temperature [°C]
20
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
6.50
3.00
6.50
3.00
6.50
Power consumption [kW]
1.80
2.63
1.86
2.67
1.89
2.67
Tab. 18: Exterior temperature 20°C
Exterior temperature [°C]
35
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
6.20
3.00
6.50
3.00
6.50
Power consumption [kW]
2.18
3.14
2.27
3.20
2.27
3.12
Tab. 19: Exterior temperature 35°C
Exterior temperature [°C]
44
Setpoint [°C] ± 2 K
22
25
28
Cooling output [kW] min./max.
3.00
4.00
3.00
4.00
3.00
5.00
Power consumption [kW]
1.66
1.80
1.72
1.96
1.80
2.25
Tab. 20: Exterior temperature 44°C