REVOLUTION SP FAN
16
Pub. No. RFSP Rev. 5 - December 2010
CONTROL BOX MOUNTING
Mount the control box securely to a wall or building column with appropriate anchors (not
provided). The box should not be greater than 200 ft. (61m) from the fan it is controlling. The fan
should be visible from where the control box is mounted. Mount the VFD control box in a location
where it will still be accessable for troubleshooting.
The electrical system (ground system, insulation etc.) must be verified by an authorized
electrician before fan is put into operation. The verification data should be entered in a record
and be stored by the customer.
RECOMMENDED FUSE RATINGS
Recommended Branch
Recommended
Circuit Protection
Incoming Service
Input Voltage
Amps
Amps
110-120V, 1PH, 60 Hz.
20A
20A
200-240V, 1PH, 60 Hz.
15A
15A
200-240V, 3PH, 60 Hz.
15A
10A
460-480V, 3 PH, 60 Hz.
15A
6A
380V, 3PH, 50 Hz.
15A
6A
575V, 3PH, 60 Hz.
10A
6A
INPUT WIRING
Bring the input wires into the bottom of the fuse block. Tighten the screws to secure the wires.
Insert the wires that are going to the motor into the contact blocks that are labeled U, V, W.
Insert the ground wire into the green contact block.
MOTOR RATING
Motor
Input Voltage
Volts
Freq.
F.L.A
200-240V, 1PH, 60 Hz.
230
60
3.2
200-240V, 3PH, 60 Hz.
400
60
3.2
460-480V, 3 PH, 60 Hz.
460
60
1.6
380V, 3PH, 50 Hz.
380
50
1.8
Increasing the speed of the fan beyond
factory set limits is not recommended and
can shorten the life of the motor.
WA R N I N G ! ! !
!
Summary of Contents for REVOLUTION SP
Page 13: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 13 CONTROL BOX WIRING...
Page 15: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 15 REMOTE MOUNTED FAN FOR SCHNEIDER ELECTRIC...
Page 29: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 29 NOTES...
Page 30: ...REVOLUTION SP FAN 30 Pub No RFSP Rev 5 December 2010 NOTES...
Page 31: ...REVOLUTION SP FAN Pub No RFSP Rev 5 December 2010 31 NOTES...