INSTALLATION
Step 8 – Fan Electrical Installation
(TYPICAL)
Fan Control Box
(14in x 16in x 8in
VFD Enclosure)
Line Voltage
Line Voltage
Fan Motor
Disconnect
Incoming Power from
End User Supplied
Branch Circuit
Protective Device
Motor Voltage
160ft [50m] Max Motor Run
Fan Motor
3ɸ
B
A
A Mount Fan Control Box (VFD Enclosure) at maintenance accessible height
B Mount disconnect at accessible height, according to local code
Mount Fan Control Box (A) and disconnect (B) safely outside the fan diameter
Field Wiring
Power/High Voltage
Incoming Power
Terminated at
F1, F2, F3
Fuse Holder
Incoming Power from
End User Supplied
Branch Circuit
Fan Motor
Disconnect
Fan Control Box
To Fan Motor
Terminal Torque 20lb‑in Max
ACCTPOABLTE:
Unshielded Stranded Conductor Types:
THHN/THWN in Metallic Conduit
Shielded Stranded Cable Types:
Belden 29501
AlphaWire V16014
Use copper wire only, minimum 600V 75°C
NOTE:
‑ If fan runs backwards
swap 2 motor wires
- L3 not used on 1ɸ fans.
Copper conductors only
14‑8 AWG, 75°C min
Control/Low Voltage
Radio PCB
Jumper Wire
DO NOT
Remove
Optional
Temperature
Sensor
Enable Jumper:
Opening the factory installed jumper between
S1 and SC will cause the fan to initiate a
controlled stop These points may be wired to
a contact from a fire system or BMS to stop the
fans during an alarm or water flow event.
OUT
Patch cord
Blue
White
Yellow
Brown
Red
Grey
Orange
Black
Figure 9
Figure 10